期刊文献+

基于不平衡过电压动态抑制的谐振接地配电网单相接地故障保护新方法 被引量:35

A new method of single-phase grounding fault protection for a resonant grounding distribution network based on unbalanced overvoltage dynamic suppression
下载PDF
导出
摘要 现有配电网单相接地故障保护技术在高阻接地故障时无法可靠启动,选相与选线结果易受三相不对称的影响。针对这一问题,提出了基于不平衡过电压动态抑制的谐振接地配电网单相接地故障保护新方法。在三相不平衡过电压动态抑制的基础上,分析了故障前后注入电流与馈线零序电流特征。根据故障发生后注入电流变化量特点构建了接地故障动态感知判据,利用注入电流变化量的相角与幅值分别进行故障相识别与过渡电阻计算,通过比较各馈线零序电流变化量有效值进行故障选线。通过PSCAD/EMTDC仿真软件对所提方法进行验证,结果表明所提方法能够准确识别高阻接地故障,选相与选线结果不受三相不平衡与系统对地电容大小影响。 The existing single-phase grounding fault protection method for distribution network cannot be reliably started when a high resistance grounding fault occurs.The results of fault phase selection and fault line selection are greatly affected by three-phase imbalance.To solve the above problem,a new method of single-phase grounding fault protection for a resonant grounding distribution network based on unbalanced overvoltage dynamic suppression is proposed.Based on the dynamic suppression of a three-phase unbalanced overvoltage,the characteristics of injection current and feeder zero sequence current before and after the phase-to-ground fault are analyzed.Given the characteristics of the injection current variation,the dynamic perception criterion of grounding fault is constructed.The fault phase selection and the transition resistance calculation are carried out by adopting the phase and root-mean-square value of the variation respectively and the fault line selection is carried out by comparing the amplitude of the zero-sequence current variation for each feeder.The PSCAD/EMTDC simulation results show that the proposed method can be started accurately for a high resistance ground fault,and the results of phase selection and line selection are not affected by the three-phase imbalance and the capacitance to ground.
作者 刘战磊 曾祥君 喻锟 刘斯琪 李理 胥鹏博 LIU Zhanlei;ZENG Xiangjun;YU Kun;LIU Siqi;LI Li;XU Pengbo(School of Electrical and Information Engineering,Changsha University of Science and Technology,Changsha 410114,China)
出处 《电力系统保护与控制》 CSCD 北大核心 2021年第8期41-49,共9页 Power System Protection and Control
基金 国家自然科学基金重点项目资助(51737002,51807012) 湖南省教育厅科技项目资助(18k047)。
关键词 三相不平衡 单相接地故障感知 故障相识别 故障选线 three-phase imbalance phase-to-ground fault perception fault phase selection fault line selection
  • 相关文献

参考文献19

二级参考文献210

共引文献289

同被引文献542

引证文献35

二级引证文献181

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部