摘要 本文针对韩城某5000t花椒冷藏库,建立了冷风机-纤维空气分布系统-货物-库内空气环境的空气流动与传热的三维计算模型。在保持总送风量不变情况,将半圆式纤维空气分布系统改进为四分之一圆式风管,以不均匀系数和余热排出效率为评价指标,对比研究了冷藏库内的速度场和温度场。结果显示,改进送风方式后,货物区温度不均匀系数最大可降低17.8%,库内余热排出效率最大可提高12.5%。 Taking the cold storage of pepper in Hancheng as research object,a three dimension physical and numerical model for flow and heat transfer inside the air-cooler-fiber air dispersion system-cargo-air in the cold storage was developed.Keeping the total air supply volume unchanged,the semi-circular fiber air dispersion system was improved into a quarter-circle fiber air dispersion system.The uniformity coefficient and the residual heat discharge efficiency were used as evaluation indexes.Then temperature Field and the velocity field in the cold storage was compared.The results show that the temperature unevenness coefficient in the cargo area can be reduced by up to 17.8%and the residual heat removal efficiency in the cold storage can be increased by up to 12.5%after the improved air supply mode.
作者 郭晋楠 南晓红 刘立军 GUO Jin-nan;NAN Xiao-hong;LIU Li-jun(School of Building Services Science and Engineering,Xi’an University of Architecture and Technology,710055;School of Energy&Power Engineering,Xi’an Jiaotong University)
出处 《建筑热能通风空调》 2020年第9期80-84,共5页 Building Energy & Environment
基金 陕西省自然科学基础研究计划项目(2018JM3038)。
关键词 冷藏库 纤维空气分布系统 温度不均匀系数 余热排出效率 cold storage fiber air dispersion system temperature uniformity coefficient residual heat removal efficiency
  • 相关文献

参考文献4

二级参考文献24

  • 1谢晶,瞿晓华,徐世琼.冷藏库内气体流场数值模拟与验证[J].农业工程学报,2005,21(2):11-16. 被引量:71
  • 2谢晶,吴天.小型冷库开关门过程温度场的数值模拟[J].上海水产大学学报,2006,15(3):333-339. 被引量:28
  • 3张祉祐.气调贮藏和气调库[M].北京:机械工业出版社,1994.. 被引量:2
  • 4陶文铨.数值传热学[M].西安:西安交通大学出版社,2005 被引量:23
  • 5陶文铨.数值传热学[M].西安:西安交通大学出版社.2002. 被引量:30
  • 6Foster A M, Barrett R, James S J, et al. Measurement and prediction of air movement through doorways in refi'igemted rooms[J]. International Journal of Refrigeration, 2002, 25(8): 1102- 1109. 被引量:1
  • 7Foster A M, Swain M J, Barrett R. Experimental verification of analytical and CFD predictions of infiltration through cold store entrances[J]. International Journal of Refrigeration, 2003, 26(8): 918- 925. 被引量:1
  • 8Foster A M, Swain M J, Barrett R, et al. Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration[J]. International Journal of Refrigeration, 2006, 29(5): 692-699. 被引量:1
  • 9Foster A M, Swain M J, Barrett R, et al. Three- dimensional effects of an air curtain used to restrict cold room infiltration[J]. Applied Mathematical Modelling, 2007, 31(6): 1109- 1123. 被引量:1
  • 10Xie J, Qu X H, Shi J Y, et al. Effect of design parameters on flow and temperature fields of a cold store by CFD simulation[J]. Journal of Food Engineering, 2006, 77(2): 355-363. 被引量:1