期刊文献+

负相序供电对馈线终端影响分析 被引量:7

Analysis of Influence of Negative Phase Sequence Power Supply on Feeder Terminal
下载PDF
导出
摘要 受现场各类因素影响,时常发生配电线路安装或换相后,因未及时核相而导致馈线终端装置处于负序供电状态,影响了FTU装置的正常运行。首先分析了FTU双电源供电工作原理,然后研究了FTU的保护配置和逻辑。根据负序运行特点,得出负相序供电可能会损坏FTU电源和造成保护误动或拒动,然后提出FTU增加相序报警、相序自调整功能等解决方法。结合山东某地负序供电运行案例,验证了负相序运行对FTU的影响,所提方法可以有效地增加FTU运行可靠性和提高配网线路管理效率。 Affected by various factors on site,after distribution line installation or phase change,feeder terminal unit (FTU) often operates in a state of negative sequence power supply due to no timely phase-check,which affects the normal operation of the FTU. This paper first analyzes the working principle of FTU dual power supply,and then makes a study on the protection configuration and logic of FTU. From the characteristics of negative sequence operation,it is derived that negative phase sequence power supply may damage FTU power supply and cause protection misoperation or rejection. The paper also proposes the solution of adding phase sequence alarm and phase sequence self-adjustment function of FTU. Finally the paper employs a case of negative sequence power supply in Shandong province to verify the effect of negative sequence operation on FTU,demonstrating that the proposed method can effectively improve the reliability of FTU operation and the line management efficiency of distribution network.
作者 曾先锋 朱中华 侯炜 王杰 王霄翔 ZENG Xianfeng;ZHU Zhonghua;HOU Wei;WANG Jie;WANG Xiaoxiang(NR Electric Co. Ltd.,Nanjing Jiangsu 211102,China)
出处 《湖北电力》 2019年第1期39-43,60,共6页 Hubei Electric Power
基金 国家电网公司科技项目(项目名称:交直流混合配电网分层分区域继电保护方案研究与装置研制)
关键词 馈线终端(FTU) 负序供电 相序报警 相序自调整 feeder terminal unit negative sequence power supply phase sequence alarm phase sequence self-adjustment
  • 相关文献

参考文献11

二级参考文献64

共引文献153

同被引文献66

引证文献7

二级引证文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部