摘要 以通辽发电总厂600MW直接空冷机组为研究对象,给出了不同的环境温度和运行工况下空冷机组最优经济背压值,实现了背压控制设定值的自动设定功能,避免了手动设定背压值对机组运行经济性的影响。对空冷系统冬季防冻保护控制逻辑进行了优化,实现了空冷系统的全过程自动控制,提高了空冷机组运行的经济性和安全性。 Taking 600 MW direct air-cooling unit in Tongliao General Power Plant as the object of study,the optimal back-pressure values of the said air-cooling unit under different ambient temperatures and different operating conditions have been given,the automatic setting function of the set values in back-pressure control being realized,avoiding the influence of manual setting back-pressure upon the economic efficiency in operation of the unit.The protecting logic for anti-freeze in winter has been optimized,the whole process automation of air-cooling system being realized,enhancing the economic efficiency and safety in operation of said air-cooling unit.
作者 孔德奇
机构地区 通辽发电总厂
出处 《热力发电》 CAS 北大核心 2011年第3期89-92,共4页 Thermal Power Generation
关键词 600MW机组 直接空冷 背压 防冻保护功能 控制 600MW unit direct air-cooling back-pressure anti-freeze protection function control
  • 相关文献

参考文献4

  • 1温高主编..发电厂 空冷技术[M].北京:中国电力出版社,2008:173.
  • 2杨其国.600MW直接空冷机组汽轮机技术特点[A].空冷汽轮机学术研讨会论文集[C].2001. 被引量:1
  • 3边立秀 周俊霞.热工控制系统[M].北京:中国电力出版社,2001.. 被引量:41
  • 4西安热工研究院有限公司.空冷系统动态特性及控制方式研究[R].2008. 被引量:1