摘要
忠武输气管道投产以来多次发生气液联动阀误关断事故。分析结果表明,设备选型不当导致供电系统不可靠以及设备本身缺陷是阀误关断的主要原因。提出了改进供电系统、加强绝缘保护、完善控制软件等整改措施。
Faulty shut-off operation of gas-liquid valve had occurred time after time in Zhongxian-Wuhan Gas Transmission Pipeline after its commissioning.Analysis results display that one of the mam causes of the faulty shut-off operation in the gas-liquid valve is the misselection of equipment.which results in low reliability of power supply system,and the other is the defects existed in equipment itself.Technical modification measures on improving power supply system,strengthen insulating protection and perfecting control software are proposed.
出处
《油气储运》
CAS
北大核心
2009年第9期33-36,共4页
Oil & Gas Storage and Transportation
关键词
气液联动阀
误关断
技术改造
故障
gas-liquid valve.faulty shut-off operation.technique.improvement