SVC广域辅助控制阻尼区域间低频振荡 被引量:48

SVC Supplementary Controller Based on Wide Area Signals to Enhance Damping of Inter-Area Oscillation
下载PDF
导出
摘要 SVC已经广泛应用于电力系统的无功支持和电压控制,广域测量系统在国内外也已有许多工程应用。本文利用广域测量信号为输入设计SVC的附加阻尼控制(PSDC)。首先阐述了SVC提供阻尼的机理,然后提出了综合留数指标的概念,并据此选择具体的控制输入信号;接着基于测试信号法和留数根轨迹方法相结合进行PSDC的参数设计;并利用PSS/E进行了特征值分析和时域仿真分析验证了所设计的附加阻尼控制器的有效性。最后针对国内某实际电网外送工程中安装的SVC设计了相应的阻尼控制器,时域仿真证明了SVC广域附加阻尼控制的有效性。 SVC is used in power system for the purpose of reactive power support and voltage control. Wide area measurement system (WAMS) has been widely used in modem power systems. This paper describes a systematic approach to design a SVC supplementary controller for improving the damping of power system oscillation (PSDC) based on wide area signals. Firstly the principle of SVC oscillation damping is described. Secondly the concept of synthetical residue index is given and is used to choose the proper input wide area signal. Then the test signal method and residue root locus are adopted to design controller parameters. The third part of the paper proves the effectiveness of the method by eigenvalue analysis and time domain simulation. Then in the last part of the paper the SVC supplementary control is applied to a real grid. And the control effect is shown by time domain simulation in a simple example and a real grid.
作者 常勇 徐政
机构地区 浙江大学电机系
出处 《电工技术学报》 EI CSCD 北大核心 2006年第12期40-46,共7页 Transactions of China Electrotechnical Society
基金 国家自然科学基金资助项目(50277034)。
关键词 广域测量控制系统 SVC 综合留数指标 测试信号法 PSS/E WAMS, SVC, synthetical residue index, test signal method, PSS/E
  • 相关文献

参考文献6

二级参考文献68

  • 1[1]Phadke A G.Synchronized phasor measurements in power system [J].IEEE computer application in power,1993,6(2):10-15. 被引量:1
  • 2[3]Wu Jintao,Kong Wongchi,Han Yingduo,et al.Dynamic monitoring and control system based on synchronized phasor measurement in Heilongjiang eastern power system [C].IEEE Power Engineering Society Winter Meeting,Singapore,2000,3:1689-1693. 被引量:1
  • 3[8]Cresap R L,Scott D N,Mittelstadt W A,et al.Operating Experience with Modulation of the Pacific HVDC Inter-tie [J].IEEE Trans on Power Apparatus and Systems,1978,97(4):1053-1059. 被引量:1
  • 4[9]Martin D E,Wong W K,Dickmander D L,et al.Increasing WSCC power system performance with modulation controls on the Intermountain Power Project HVDC system [J].IEEE Trans on Power Delivery,1992,7(3):1634-1642. 被引量:1
  • 5[10]strup T.Infuluence of angle control on then dynamic behaviour of power systems [J].Control Engineering Practice,1998,6(12):1435-1563. 被引量:1
  • 6[11]Kundur P.Power system stability and control [M].Electrical Engineering Series:McGraw-Hill,1994:700-822 and 1151-1160. 被引量:1
  • 7[12]Hauer J F.Application of Prony analysis to the determination of modal content and equivalent models for measured power system response[J].IEEE Trans on Power System,1991,6(3):1062-1068. 被引量:1
  • 8[14]Hongxia Wu,Hui Ni,Heydt G T.The impact of time delay on robust control design in power systems[C].IEEE PES Winter Meeting,New York,2002,2:1511-1516. 被引量:1
  • 9[15]Snyder A F,Hadjsaid N,Georges D,et al.Inter-area oscillation damping with power system stabilizers and synchronized phasor measurements[C].POWERCON′98,Beijing,1998,2:790-794. 被引量:1
  • 10韩英铎 许树楷 谢小荣.电力系统监控技术的新方向—基于同步相量技术的广域动态安全监测与控制系统.信息通信与电力自动化,2004,(3):12-14. 被引量:1

共引文献316

同被引文献649

引证文献48

二级引证文献501

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部