期刊文献+

信号电涌保护器电路设计中去耦电阻的选择 被引量:7

Selecting Decoupling Resistance in the Design of Surge Protective Devices Connected to Telecommunications and Signaling
下载PDF
导出
摘要 分析了由气体放电管、电阻、暂态抑制二极管组成的BNC型信号电涌保护器的保护电路,对该保护电路进行了传输特性测试和标称放电电流的冲击实验。结果表明,放电管与暂态抑制二极管在去耦电阻阻值为2.2Ω情况下配合,保护电路在规定的通频带下不仅传输特性较好,而且冲击后的残压也较低。 The type of BNC signaling surge protection circuit, consisting of gaseous discharge tube, resistante, transient diode was analyzed. Results of the transfer characteristics test and the impulse test with nominal discharging current show that when R is 2.2 Ω, not only the protection circuit has good transfer characteristics under specified passband, but also its residual voltage is lower.
出处 《低压电器》 北大核心 2006年第4期13-15,共3页 Low Voltage Apparatus
关键词 电涌保护器 气体放电管 去耦电阻 通频带 surge protective device(SPD) gaseous discharge tube decoupling resistance passband
  • 相关文献

参考文献4

二级参考文献3

  • 1Standler R B.Transients on the Mains in a Residential Environment[J].IEEE Trans.on electromagnetic compatibility, 1989, 31(2): 170-176. 被引量:1
  • 2ANSI/IEEE C62.41-1980, IEEE Guide for Surge Voltages in Low-Voltage AC Power Circuits[S]. 被引量:1
  • 3易事达三联科技有限公司.六点防雷方案中之浪涌保护的探讨[J].工科物理,1998,1:57-58. 被引量:1