埋地换热器换热性能是地源热泵设计基础,针对不同埋管方式埋地换热器建立了砂石回填单 U 型、双 U 型井埋管和混凝土回填单 U 型井埋管的单井实验系统,开展埋地换热器单井的换热性能实验研究。研究了不同的土壤物性、回填材料、埋管数...埋地换热器换热性能是地源热泵设计基础,针对不同埋管方式埋地换热器建立了砂石回填单 U 型、双 U 型井埋管和混凝土回填单 U 型井埋管的单井实验系统,开展埋地换热器单井的换热性能实验研究。研究了不同的土壤物性、回填材料、埋管数量和运行工况下单井换热器换热性能。展开更多
Aiming at the ground-coupled source heat pump that possesses the shortcomings of occupying larger land,this article studies the heat exchanged of heat exchanger in piling,and compares it with common heat exchangers bu...Aiming at the ground-coupled source heat pump that possesses the shortcomings of occupying larger land,this article studies the heat exchanged of heat exchanger in piling,and compares it with common heat exchangers buried directly. The result indicates that the heat exchanger makes the best use of structure of building,saves land,reduces the construction cost,and the heat exchanged is obviously more than exchangers buried directly. In winter condition,when W-shape pipe heat exchanger in pile foundation is 50 m deep and diameter is 800 mm,it transfers 1.2-1.3 times as large as the one of single U-shape buried directly at the flow rate of 0.6 m/s,whose borehole diameter is 300 mm. And in summer condition it does about 2.0-2.3 times as that of U-shape one.展开更多
基金Project(2006BAJ03A10) supported by the National Key Technology R&D Program of China
文摘Aiming at the ground-coupled source heat pump that possesses the shortcomings of occupying larger land,this article studies the heat exchanged of heat exchanger in piling,and compares it with common heat exchangers buried directly. The result indicates that the heat exchanger makes the best use of structure of building,saves land,reduces the construction cost,and the heat exchanged is obviously more than exchangers buried directly. In winter condition,when W-shape pipe heat exchanger in pile foundation is 50 m deep and diameter is 800 mm,it transfers 1.2-1.3 times as large as the one of single U-shape buried directly at the flow rate of 0.6 m/s,whose borehole diameter is 300 mm. And in summer condition it does about 2.0-2.3 times as that of U-shape one.