期刊文献+

35kV干式变压器高压绕组结构和绝缘的优化及验算

Optimization and Checking Calculation of High Voltage Winding Structure and Insulation of 35kV Dry-type Transformer
下载PDF
导出
摘要 本文作者对一台35kV干式变压器进行了主纵绝缘计算。经过对计算结果的分析,结合该台产品的结构特点,对其高压绕组结构进行优化,并减少高压-低压、高压相间主距绝缘尺寸。通过波过程和电场仿真软件的再次验算,调整后的结构满足绝缘要求,验证了结构改进优化的可行性。 In this paper,the main and longitudinal insulation of a 35kV dry-type trans former is calculated.Based on the analysis of the calculation results,the structure of high voltage winding is optimized,and the insulation size of high-voltage to low-voltage and high-voltage phase-to-phase is reduced.Through the wave process and the elec tric field simulation software,the adjusted structure meets the insulation requirements,which verifies the feasibility of structural improvement and optimization.
作者 张婷婷 范俊锋 杜学奇 李玮 刘一博 ZHANG Tingting;FAN Junfeng;DU Xueqi;LI Wei;LIU Yibo(Shenyang Transformer Research Institute Co.,Ltd.,Shenyang 110000,China)
出处 《变压器》 2024年第4期1-5,共5页 Transformer
关键词 干式变压器 波过程 主纵绝缘 结构优化 Dry-type transformer Wave process Main and longitudinal insulation Struc ture optimization
  • 相关文献

参考文献15

二级参考文献181

共引文献75

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部