期刊文献+

核电厂除盐水系统连通管线水质超标原因分析

Analysis of Water Quality Exceeding the Standard in the Connecting Pipeline of Demineralized Water System in Nuclear Power Plant
下载PDF
导出
摘要 某核电厂除盐水系统连通管线改造完成后,连通管线内的水在静置一定时间后,Na^(+)和SO^(2-)_(4)含量偏大超标。本文根据现场实际工况制作了试验装置,并对一系列浸泡试验进行离子含量分析,结果表明,管道母材20#钢是导致管内介质Na^(+)和SO_(4)^(2-)含量超标的主要因素。 After the reconstruction of the connecting pipeline of the demineralized water system in a nuclear power plant,the content of Na^(+) and SO_(4)^(2-) in the connecting pipeline was too large and exceeded the standard after the water in the connecting pipeline was left standing for a certain time.In this paper,a test device is made according to the actual working conditions,and the ion content of a series of immersion tests is analyzed.The results show that the base material 20#steel of the pipeline is the main factor causing the content of Na^(+)and SO_(4)^(2-) in the medium in the pipeline to exceed the standard.
作者 赵永明 方江 张维 刘洪群 ZHAO Yong-ming;FANG Jiang;ZHANG Wei;LIU Hong-qun(CNNC Nuclear Power Operations Management Co.,Ltd.Haiyan 314300,China;Suzhou Nuclear Power Research Institute,Suzhou 215004,China)
出处 《全面腐蚀控制》 2023年第2期52-54,共3页 Total Corrosion Control
关键词 除盐水系统 水质 管道母材 焊缝 demineralized water system water quality base material of pipeline welding line