反渗透技术在高硬度高含盐量地下水中的应用研究 被引量:5

Application Study of Reverse Osmosis Technology in Treating High Hardness and High Salt Content Groundwater
下载PDF
导出
摘要 针对某地高含盐量高硬度地下水的特点,选择BW30-4040复合膜,采用二级反渗透工艺系统对其进行处理,以期达到内燃机车冷却水标准.试验考察了操作压力对产水量、脱盐率、回收率的影响,并根据溶解—扩散理论模型对实验结果进行了分析.通过运行试验,分析研究了与膜性能密切相关的主要参数的变化,并对膜的结垢倾向进行了分析.该系统的成功运行对广大西北铁路地区内燃机车冷却水的处理具有一定的借鉴作用. In view of characteristic of high salt content and high hardness of ground water, BW30-4040 composite membrane was adopted. Groundwater was treated through two-stage reverse osmosis craft in order to achieve the diesel locomotive cooling water standard. Influences of operating pressure to permeate flow and recovery and desalting rate have been inspected by the experiment, whose result has been analysed by dissolution and proliferation theoretical model. The rarity of main parameters relating to intimately membrane performance has been analysed by operation test. And the membrane scaling leaning has been also analysed. This system successful operation offers certain reference function for treatment of the vast northwest railway regional diesel locomotive cooling water.
作者 武福平
出处 《兰州交通大学学报》 CAS 2006年第1期55-58,共4页 Journal of Lanzhou Jiaotong University
关键词 二级反渗透 BW30-4040膜 除盐水 two-stage reverse osmosis BW30-4040 membrane deionized water