35 kV金属封闭开关柜局放导致绝缘损坏是开关柜事故发生的主要原因。对某变电站35 kV开关柜开展带电局放检测,发现了异常局放信号。采用声电联合的方法进行了局放定位,并对试验数据进行分析研究,得到了产生异常的位置及放电原因,为运行单位提供了处理意见,也为类似局放异常分析提供了借鉴方法。
The insulation damage caused by partial discharge of 35 kV metal-enclosed switchgear is the main cause of switchgear accidents.An abnormal partial discharge signal was found during live partial discharge detection of 35 kV switchgear in a substation.Localization of partial discharge was carried out by using the method of sound electricity combination,and the test data was analyzed and studied.The location of abnormal discharge and the cause of discharge were obtained,which provides the handling suggestions for the operating unit,and also provides a reference method for the analysis of similar partial discharge abnormalities.