期刊文献+

变电站35 kV开关柜套管烧毁分析与改进措施 被引量:1

Analysis and Improvement Measures for the Bushing Burnout of 35 kV Switchgear in a Substation
下载PDF
导出
摘要 本文针对变电站35 kV开关柜套管多次烧毁问题,通过电能质量测试数据分析,得到谐波指标超过国标限值,其它电能质量指标均未超过国标限值,经过溯源定位谐波源来自于35 kV侧,35 kV侧谐波电流注入系统高压侧110 kV,对故障时录波文件分析谐波伴随存在变压器合闸涌流。通过变电站出线用户现场调研、分析计算,得到变电站套管的烧毁是由过电压引起的,很大可能是由5次谐波并联谐振放大、变压器合闸涌流等多个因素导致的,并提出多条针对性建议。 Aiming at solving the problem of the multiple burnouts of the 35 kV switchgear bushings in a substation,it was found that the harmonic index exceeded the national standard limit through the analysis of power quality test data in this paper,while other power quality indicators did not exceed the national standard limit.The harmonics were traced to the 35 kV side of the system,whose harmonic current is injected into the 110 kV side.Through analysis of the oscillographic fault record,it is revealed that the harmonic current was accompanied by the closing inrush current of the transformer.Through field investigation,analysis and calculation,it is concluded that the burnout of substation bushings was caused by overvoltage,which is likely to be caused by the 5th harmonic parallel resonance amplification,the closing inrush current of the transformer and other factors,and several targeted suggestions are proposed.
作者 郭敏 姚知洋 梁广生 覃斌 吴晓锐 GUO Min;YAO Zhiyang;LIANG Guangsheng;QIN Bin;WU Xiaorui(Electric Power Research Institute of Guangxi Power Grid Co.,Ltd.,Guangxi Nanning 530023,China;Baise Power Supply Bureau of Guangxi Power Grid Co.,Ltd.,Guangxi Baise 533000,China;Debao Power Supply Bureau of Guangxi New Power Investment Group Co.,Ltd.,Guangxi Baise 533000,China)
出处 《广西电力》 2022年第2期62-66,共5页 Guangxi Electric Power
关键词 套管 谐振放大 合闸涌流 电容器 电能质量 bushing resonance amplification closing inrush current capacitor power quality
  • 相关文献

参考文献5

二级参考文献34

共引文献62

同被引文献4

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部