摘要
构建了风火储一体化电站,在假设燃煤机组达到无惯性延迟响应且储能电池可秒级切换充放电状态的极限情况下,规划适配该风火储一体化电站的优化调度策略;从电力波动率、弃电率和电力缺额率3个功率特性角度对风火储一体化电站与区域独立电站进行对比,并采用Matlab进行仿真验证。结果表明:相比区域独立电站,风火储一体化电站的电力波动率从1.306%降至0.178%,弃电率从0.667%降至0.145%,电力缺额率从0.643%降至0.010%,大幅提高了对AGC负荷指令的响应能力。
A wind-coal-battery coupling integrated power station was constructed,and the optimal scheduling strategy of the proposed power station was planned under the assumption that the coal-fired unit can reach no inertia delay response and the energy storage battery can switch the storage/release state in seconds.Besides,the proposed power station was compared with regional independent power station from the following aspects,such as power volatility rate,power abandonment rate and power shortage rate,which was verified by Matlab software.Results show that compared with regional independent power station,power volatility rate of the proposed power station decreases from 1.306% to 0.178%,power abandonment rate decreases from 0.667% to 0.145%,and power shortage rate decreases from 0.643% to 0.010%,indicating that the proposed power station greatly improves its response ability to automatic generation control(AGC) load command.
作者
张磊
郭语
石嘉豪
孙恩慧
张倩
李永毅
ZHANG Lei;GUO Yu;SHI Jiahao;SUN Enhui;ZHANG Qian;LI Yongyi(Department of Power Engineering,North China Electric Power University,Baoding 071003,Hebei Province,China;Hebei Key Laboratory of Low Carbon and High Efficiency Power Generation Technology,North China Electric Power University,Baoding 071003,Hebei Province,China)
出处
《动力工程学报》
CAS
CSCD
北大核心
2022年第6期568-574,581,共8页
Journal of Chinese Society of Power Engineering
基金
国家自然科学基金资助项目(52076079)
河北省自然科学基金资助项目(E2020502013)
中央高校基本科研业务费资助项目(2021MS079,2021MS076)。
关键词
风力发电
燃煤电站
AGC负荷指令
储能电池
功率特性
wind power generation
coal-fired power station
AGC load command
energy storage battery
power characteristic