期刊文献+

GIS设备最低环境温度的风险评估 被引量:4

Risk Assessment of Minimum Design EnvironmentalTemperature for GIS Equipment
下载PDF
导出
摘要 气体绝缘开关(GIS)设备需要根据最低气温选择气密元件,在超设计低温情况下存在因气密元件异常而出现大面积泄漏事故导致设备无法正常运行的风险。选取山东省内9个站点为研究对象,收集了1973~2016年间气温观测数据,使用基于广义极值(GEV)分布的年极值法,计算了按现行规程确定的多年平均气温进行设计选型遭遇超设计低温的风险水平,并按当地历史观测最低气温及按典型地区最低气温确定最低设计气温时遭遇超设计低温的风险进行了评估,为优化调整输变电设备的设计气温提供了理论支持和应用参考。 Sealing component of GIS equipment is selected according to the criterion of minimum temperature,and there is a risk that the equipment cannot operate normally due to the large area leakage accident caused by abnormal air tightness element under the condition of super design low temperature.Meteorological data from 1973 to 2016 in 9 sites in Shandong are investigated in this paper.The annual minimum temperatures are singled out to estimate the risk of extreme temperature lower than the design criterion with generalized extreme value(GEV)according to existing specification.Thereafter,the improved approach to decide design criterion is proposed and the associated risk is estimated.
作者 付青 陈海炎 伍亚萍 逯文佳 李永明 FU Qing;CHEN Haiyan;WU Yaping;LU Wenjia;LI Yongming(Changsha University of Science and Technology,Hunan Province Innovation Center of Renewable Energy&Smart Grids,Changsha 410004,China;Electric Power Planning&Engineering Institute,Beijing 100120,China;State Grid Beijing Electric Power Corporation,Beijing 100120,China;State Grid Shandong Maintenance Corporation,Ji’nan 250080,China)
出处 《电器与能效管理技术》 2021年第3期18-23,共6页 Electrical & Energy Management Technology
关键词 平均最低温度 GIS设备 超设计低温概率 风险评估 极值分布 mean minimum temperature GIS equipment ultra-design low temperature probability risk assessment extreme value distribution
  • 相关文献

参考文献11

二级参考文献68

共引文献69

同被引文献45

引证文献4

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部