期刊文献+

150t直流电弧炉SVC改造实践 被引量:3

The Revamping Practice of SVC to 150 t DC EAF
下载PDF
导出
摘要 原有SVC装置对直流电弧炉在冶炼过程中产生的谐波电流和无功起到了很好的吸收、补偿作用,但经20年运行,逐步出现了一系列问题。在此分析了原有SVC控制下存在的电能质量问题,详细介绍了设备改造原则,主要包括谐波叠加计算、模型建立、SVC补偿容量确定、滤波器设计原则、滤波器设计以及滤波器安全性能校核等,并给出了改造结果。SVC改造后电网中的各项参数和指标得到了有效改善,电网电能质量提升,系统运行可靠性也得到提高。 The original SVC device can absorb and compensate harmonic current and reactive power produced by DC EAF in smelting process, but after 20 years of operation,a series of problems have gradually emerged.The power quality problems under the control of the original SVC are analyzed,the principle of equipment transformation is introduced in detail,it mainly includes harmonic superposition calculation,model building,determination of SVC compensation capacity, filter design principle, filter design and filter safety performance checking.Various parameters and indicators of power grid have been effectively improved after SVC modification, the power quality and operational reliability of the system have been improved effectively.
作者 顾建军 周建平 GU Jian-jun;ZHOU Jian-ping(Baoshan Iron & Steel Co.,Ltd.,Shanghai 200941,China)
出处 《电力电子技术》 CSCD 北大核心 2019年第5期42-44,56,共4页 Power Electronics
关键词 直流电弧炉 无功功率 谐波 DC EAF passive power harmonics
  • 相关文献

参考文献5

二级参考文献30

共引文献75

同被引文献49

引证文献3

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部