贯流式水轮发电机空冷器爆管漏水分析与处理 被引量:1

Analysis and Treatment of Broken Pipe and Water Leakage of Air Cooler in Tubular Turbine Generator
下载PDF
导出
摘要 京南电厂1号贯流式水轮发电机在投运早期,由于冷却水质不合格,对空冷器铜管造成腐蚀,此外,冷却水系统膨胀水箱气囊破裂损坏造成冷却水压不稳定,从而导致2号空冷器铜管漏水。更换膨胀水箱和采用环氧树脂封堵空冷器开裂铜管后,漏水现象消除,系统水压调节正常,满足机组安全运行需要。 The copper tube of air cooler had been corroded because of the disqualification of cooling water quality in the early operation stage of Jingnan No.1 tubular turbine generation.Besides,the damage of air bag of expansion tank in water cooling system caused the unstable cooling water pressure,which caused the water leakage of cooper tube of No.2 air cooler.After the replacement of expansion tank and the block of cracked cooper tube of the air cooler by epoxy resins,the water leakage has been eliminated and the regulation of system water pressure are normal,which satisfy the security operation of generator unit.
作者 李凌 LI Ling(Guangxi Wuzhou Guijiang Electric Power Co.,Ltd.,Guangxi Wuzhou 543011,China)
出处 《广西电力》 2018年第2期75-76,共2页 Guangxi Electric Power
关键词 膨胀水箱 空冷器 漏水 expansion tank air cooler water leakage