摘要
雷击是影响±500 k V直流架空输电线路运行的重要因素,±500 k V直流线路避雷器的挂网试运行成功,为直流线路防雷改造提供了有效技术手段,但大规模的工程应用仍是空白。笔者结合±500 k V江城线直流线路避雷器安装项目,研究了±500 k V直流线路避雷器选型、选点原则,给出了不同塔型下直流线路避雷器的安装方案,并提出直线塔宜采用悬挂式安装方案,耐张塔宜采用地面支柱式安装方案。运行数据表明,笔者提出的±500 k V直流线路避雷器选型、选点原则防雷改造效果明显,安装方案达到线路安全运行要求,对±500 k V直流线路避雷器的推广应用和在运直流线路防雷改造工作具有重要的实践和借鉴意义。
Lightning is a key factor for the safe and reliable operation of ±500 kV high voltage direct current(HVDC)transmission lines. The DC arresters, which have been successfully applied in the ±500 kV HVDC transmission lines provide an effective method to protect against lightning. Based on a practical project of JiangCheng line,a ±500 kV HVDC transmission line of South China,both the procedure of selection and the principle of installation sites for DC arresters have been discussed in detail. It shows that the suspension DC arresters are applicable for the self-supporting towers whereas the supporting DC arresters are applicable for the strain towers.The operational data verified the proposed scenario. This work not only presents useful references for the extended application of ±500 kV DC arresters, but also is significant for the reform of lightning protection measures of current operating DC transmission lines.
出处
《高压电器》
CAS
CSCD
北大核心
2016年第2期178-184,共7页
High Voltage Apparatus
关键词
±500
kV直流输电线路
直流线路避雷器
防雷保护
悬挂式
支柱式
节点板连接
紧固金具连接
±500 k V DC transmission line
DC line arrester
lightning protection
suspension type
pillar type
gusset plate connection
fastening fittings connection