期刊文献+

AP 1000核电厂除氧器暂态分析及防汽蚀控制方案 被引量:2

Transient Calculation of Deaerator and Control Scheme of Cavitation Prevention for AP1000 Nuclear Power Plants
下载PDF
导出
摘要 为提出合理的AP1000核电厂甩负荷工况下的净正吸入压头(NPSH)控制方案,有效防止运行中主给水泵组汽蚀,分析了汽蚀原理和除氧器液位控制及压力控制逻辑,并收集数据建立除氧器暂态计算模型,计算结果表明凝结水限流控制在30%及除氧器暂态压力下降率控制为0.001 77 MPa/s整定值时,可以满足主给水泵组防汽蚀控制要求,并由此提出几种典型甩负荷工况防汽蚀控制方案和优化措施,指导系统调试和运行,提高机组运行安全性。 In order to formulate a reasonable NPSH (net positive suction head) control scheme under load rejection conditions of AP1000 nuclear power plants and effectively prevent cavitation in the main feed water pumps during the operation, the cavitation mechanism and the control logics of deaerator water level and pressure are analyzed and the model for deaerator transient calculation is established based on the collected data. The calculation results show that with the setting value of the condensate flow limit at 30% and the deaerator transient pressure decreasing rate at 0.001 77 MPa/s, the NPSH requirements for the main feed water pumps can be met. Therefore, the cavitation prevention schemes and optimization methods for typical load rejection conditions are proposed as the guidance for commissioning and operation to improve the safety of nuclear power plants.
出处 《中国电力》 CSCD 北大核心 2015年第4期66-70,共5页 Electric Power
关键词 核电厂 除氧器 暂态分析 净正吸入压头 控制优化 nuclear power plant deaerator transient calculation net positive suction head control optimization
  • 相关文献

参考文献11

二级参考文献61

共引文献64

同被引文献21

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部