摘要
HGIS现场安装后,使用变频串联谐振方法进行交流耐压试验是比较有效的检测手段,通过耐压试验可以发现安装质量问题;文中的两起放电故障是通过耐压试验发现的,根据对放电原因的分析,区分放电性质,检测出故障部位,保证安装质量。
HGIS site after installation, use frequency conversion series resonance method for AC withstand voltage test is effective detection means, through the withstand voltage test the installation quality problem can be found.In this paper, the two discharge faults are found through the withstand voltage test, according to the analysis on the cause of discharge, distinguish between the discharge properties, detect the fault position, ensure the installation quality.
出处
《高压电器》
CAS
CSCD
北大核心
2013年第2期120-123,共4页
High Voltage Apparatus
关键词
HGIS安装质量
变频串谐耐压
故障分析
HGIS installation quality
frequency voltage harmonic series
failure analysis