导出
摘要 为了避免部分负荷下空调运行所造成的能量损失,需对空调水系统进行变流量控制.针对一次泵水系统,采用一种带Smith预估的模糊PID复合串级控制系统,对最不利支路上压差和冷水机组回水温度进行串级优化控制.主控制器采用模糊PID参数自调整控制器.为消除纯延迟,副回路中加入Smith预估控制器.Matlab仿真结果表明,新的串级控制系统相比常规PID控制,响应速度快,具有良好的静态性能. The control of variable water flow can avoid power losses caused by air condition under partial load.For the characteristics of the primary flow,the fuzzy PID composite serial control system with Smith predictive estimate is adopted.The main controlled variable is the temperature of chilled return water,and fuzzy PID controller of automatic regulation is used.Smith predictive estimator is adopted in the minor loop to eliminate delay,and the variable is the pressure on worst side.The Matlab simulation shows that the new serial control system,compared with general cascade control,has excellent static performance and fast response speed.
出处 《西安工业大学学报》 CAS 2012年第4期330-333,共4页 Journal of Xi’an Technological University
关键词 中央空调 模糊PID控制 Smith预估 串级控制 central air-condition fuzzy PID control smith predictive estimate cascade control
  • 相关文献

参考文献7

  • 1陈丹丹,晋欣桥.变水量空调系统的优化控制策略及其能耗分析[J].建筑热能通风空调,2009,28(4):1-5. 被引量:3
  • 2Ahn B C,Mitchell J W. Optimal Control Development for Chilled Water Plants Using a Quadratic Representation[J].Energy and Buildings,2001.371. 被引量:1
  • 3霍小平.中央空调自控系统设计[M]北京:中国电力出版社,2004. 被引量:1
  • 4王建文..中央空调水系统控制策略的研究及实现[D].西安建筑科技大学,2009:
  • 5刘金琨.先进PID控制及其MATLAB仿真[M]北京:电子工业出版社,2003. 被引量:1
  • 6Yun Li,Kiam H A,Gregory C Y. PID Control System Analysis and Design[J].IEEE Control Systems Magazine,2006,(01):32.doi:10.1109/MCS.2006.1580152. 被引量:1
  • 7诸静.模糊控制原理与应用[M]北京:机械工业出版社,1995. 被引量:1