期刊文献+

油介质损耗因数异常的原因分析及处理

Analysis on reasons of abnormal oil dielectric dissipation factor and the treatments
下载PDF
导出
摘要 华电国际邹县发电厂油介质损耗因数测量值分散性较大,测量时存在放电现象。对采集的数据进行分析后,确定测量数值变化大的原因为2801电桥存在故障。更换2801电桥的油杯引线柱接头后,油介质损耗因数测量值稳定,内部放电的问题得到了有效解决。 The measurement value of the oil dielectric dissipation factor of the Huadian International Zouxian Power Plant has larger dispersibility,and electric discharge phenomena occurred in the measurement.According to the analysis of the collected data,it was determined that the reason of the larger variation of the measured value is the fault in the 2801 type electrical bridge.After the lead column joint of the oil cup of 2801 type electrical bridge was replaced,the measured data of the oil dielectric factor became stable,and the internal electric discharge was solved effectively.
出处 《华电技术》 CAS 2011年第2期38-40,80,共3页 HUADIAN TECHNOLOGY
关键词 油介质损耗因数 测量 2801电桥 屏蔽 干扰 oil dielectric dissipation factor measurement 2801 type electrical bridge,shield interference
  • 相关文献

参考文献3

  • 1四川省电力试验研究院.高压电气设备试验方法[M].北京:中国电力出版社,2001. 被引量:4
  • 2王浩.高电压试验技术[M].北京:水利电力出版社,1995. 被引量:1
  • 3肖金泉.高电压试验工程[M].北京:清华大学出版社,2001. 被引量:1

共引文献3