风机盘管占空比模糊控制试验研究 被引量:3

Experimental Analysis on Duty Ratio Fuzzy Control for Fan-coil Unit
下载PDF
导出
摘要 提出了一类风机盘管节能控制的新方法,将占空比的概念引入风机盘管电动水阀的控制中,在特定的控制周期内充分利用水阀关闭状态下风机盘管的冷却除湿(或供热)能力,利用Mamdani模糊规则与作用模糊子集推理方法,根据室温偏差与偏差变化确定水阀占空比与风机档位。试验结果表明,风机盘管占空比模糊控制方法较传统控制方法的节能量高于30%,同时可达到更好的室温控制效果。 A new type of energy efficiency control method for fan-coil unit is presented.By introducing the conception of duty ratio into electric valve control,the cooling and dehumidifying capacity of fan-coil unit is fully utilized.By means of Mamdani type fuzzy rule and the Method of Functioning-fuzzy-subset Inference,duty ratio of valve and fan speed signal are identified according to deviation and deviation change of room temperature.It is shown that presented method could achieve at least 30% energy saving than traditional control method as well as a preferable room temperature control effect.
出处 《土木建筑与环境工程》 CSCD 北大核心 2010年第6期92-99,共8页 Journal of Civil,Architectural & Environment Engineering
基金 国家自然科学基金资助项目(50578049 51008142 51078053) 国家科技支撑计划子课题(2006BAJ01A09 2008BAJ12B05)
关键词 风机盘管 占空比 模糊控制 试验 fan-coil unit duty ratio fuzzy control experiments