期刊文献+

关于T接线路差动保护应用的特殊问题探讨 被引量:13

Discussing some special problems about application of teed line differential protection
下载PDF
导出
摘要 T接线路在110kV电压等级应用越来越广泛。T接线路面临区内故障电流流出、区外故障CT易饱和、三端运行及两端运行方式切换等特殊问题。结合许继公司研制的WXH-813A/T装置介绍了适用于T接线路的三端差动保护的原理及配置方案,并提出了与T接线路相关特殊问题的解决方案。 T connected lines in the 110kV voltage are applied more widely. T connected lines face to the special problems of the current outflow of internal fault, easy TA saturation of outside fault, three-terminal operation and two-terminal operating mode switch, and so on. Combining the WXH-813A / T developed by XJ, this paper introduces the device applied to T-connected three-side with line differential protection principle and configuration, and then proposes the solutions of the T-connected line related to the special problems.
机构地区 许继电气公司
出处 《电力系统保护与控制》 EI CSCD 北大核心 2009年第17期57-59,64,共4页 Power System Protection and Control
关键词 110 KV T接线路 特殊问题 三端差动保护 解决方案 110 kV T-connected line special problem three-terminal differential protection solution