期刊文献+

600MW空冷机组空冷岛的调试 被引量:4

COMMISION DEBUGGING OF AIR-COOLED ISLAND SYSTEMS FOR 600MW AIR-COOLED UNITS
下载PDF
导出
摘要 对国电河北龙山发电有限公司2×600 MW空冷机组空冷岛的调试中出现的问题进行了分析,如冬季停机后起动空冷岛真空下降过快,全部空冷风机全负荷运转,汽封系统漏空气空冷岛背压急剧上升等,给出了调试中对上述问题采取的相关防范措施,并对调试中部分未能解决的问题,提出了具体建议。 The problems appeared in commission debugging of the air- cooled island systems for two 600 MW air-cooled units of Guodian Longshan Power Generation Co Ltd,such as undue fast vacuum drop in air - cooled island during start - up of said units after their shutdown in winter, the rapid rise of back - pressure in said air - cooled isrand due to full - load operation of all cooling air fans and air - leakage in the steam seal system, etc. , have been analysed, and corresponding preventive measures adopted for above - mentioned problems in the commission debugging process being given; Regarding to a part of problems, which hadn't been solved in debugging,some concrete recommendations have been put forward.
出处 《热力发电》 北大核心 2009年第7期66-68,71,共4页 Thermal Power Generation
关键词 600MW空冷机组 空冷岛 真空 空冷风机 背压 600 MW air - cooled unit air - cooled island cooling air fan back - pressure vacuum
  • 相关文献

参考文献1

共引文献1

同被引文献16

引证文献4

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部