1000kV同塔双回线路双回故障跳闸概率分析 被引量:20

Analysis of Failure Trip Rate of 1000 kV Double Circuits on the Same Tower
下载PDF
导出
摘要 为给1000kV同塔双回线路提供设计前提依据,通过对我国1000kV同塔双回线路的防雷计算分析和对我国500kV同塔双回线路以及日本1000kV特高压同塔双回线路(降压500kV运行)的故障调查分析,确定我国1000kV同塔双回线路发生双回同时故障跳闸的概率接近于零。根据我国1000kV同塔双回线路的特点,提出了我国1000kV同塔双回线路设计中考虑其潜供电流水平和限制措施、过电压水平和限制措施以及绝缘配合时,均可以不考虑双回同时故障的判断。这一研究为我国1000kV线路设计前提条件的确定提供了技术依据。 We analyzed the lightning calculation of 1000 kV double-circuit line in China, the statistical operating experiences of 500 kV double circuit line in China and the UHV double-circuit transmission lines under 550 kV operation in Japan. Results show that the double circuit simultaneous failure trip rate of 1000 kV double-circuit line in China is nearly zero. Therefore, based on the characteristics of 1000 kV double-circuit line in China, double circuit simultaneous failure can be discarded on the research of the level and limitation measures of secondary arc current, the over-voltage level and limitation measures, and insulation coordination. This research provides technical support for the design of 1000 kV double-circuit line on the same tower in China.
出处 《高电压技术》 EI CAS CSCD 北大核心 2009年第3期441-444,共4页 High Voltage Engineering
基金 国家"十一五"科技支撑计划重大项目(2006BAA02A02)~~
关键词 1000 KV 同塔双回 线路 故障 跳闸率 故障类型 1000 kV double circuits on the same tower transmission line failure trip rate failure type