应用饱和盐密原理修订江苏电网污区分布图 被引量:8

Modifying pollution plots of Jiangsu Power Grid by using saturated equal salt deposit density
原文传递
导出
摘要 输电线路外绝缘污秽等级的划分关系到输电系统运行安全。对江苏电网双伞形绝缘子饱和盐密与灰密进行分析,得到饱和系数、不均匀系数和灰密比,通过典型环境的饱和盐密与灰密测量,确定其现场污秽度等级,提出了修订江苏电网污区分布图的方法。 Pollution classification for the external insulation of transmission lines directly affects system security. The saturated equal salt deposit density (ESDD) and the non-soluble deposit density (NSDD) of the double-umbrella type insulator in Jiangsu Power Grid are analyzed, and the saturation coefficient, the asymmetry coefficient, and the NSDD/ ESDD ratio are obtained. The site pollution severity (SPS) of typical environments can be identified through measurement of saturated ESDD and NSDD. Methods for modifying the pollution plot of Jiangsu Power Grid are also proposed.
作者 刘贞瑶 叶辉
出处 《华东电力》 北大核心 2008年第8期51-54,共4页 East China Electric Power
关键词 输电线路 外绝缘 饱和盐密 现场污秽度等级 污区分布图 transmission line external insulation saturated equal salt deposit density site pollution severity (SPS) pollution plot
  • 相关文献

参考文献4

二级参考文献7

  • 1.GB/T16434-1996.高压架空线路和发、变电所环境污区分级及外绝缘选择标准[S].,.. 被引量:1
  • 2宿志一 刘思湄.大气环境对输变电设备抗污闪能力的影响(总报告)[R].北京:中国电力科学研究院,1995.. 被引量:1
  • 3宿志一.北方内陆地区线路绝缘子串的直流自然积污特性[R].北京:中国电力科学研究院,1990.. 被引量:1
  • 4..1983年原水利电力部颁发的水电技术字第23号文的附件.高压架空线路和发变电所电瓷外绝缘污秽分级标准[Z].,.. 被引量:1
  • 5.国家电力公司安运[1998]223号文,关于修订电力系统污区分布图的通知[Z].,.. 被引量:1
  • 6GB/T16434-1996,高压架空线路、发电厂、变电所环境污区分级及外绝缘选择标准[S]. 被引量:1
  • 7(90)华东电生字第336号.关于颁发试行<华东电网绝缘子等值附盐密度测量方法的暂行规定>的通知[R].1990. 被引量:1