期刊文献+

电缆终端异常发热原因分析 被引量:7

Analysis of Abnormal Heat of Cable Terminals
下载PDF
导出
摘要 近年来,广州供电局应用红外热像仪检测110kV瓷套式电缆终端,发现较多电缆终端存在异常发热现象。根据实际情况,从环境因素影响、填充介质影响等方面分析引起异常发热的原因。对终端填充两种不同的硅油,进行一系列的分析试验,证明终端异常发热是由于终端绝缘介质硅油的品质不良所引起,通过更换硅油可解决该问题。 In recent years, thermal infrared imagers were used in Guangzhou Power Supply Bureau to detect 110 kV porcelain bushing type cable terminals, and many of the terminals were found to get hot abnormally. According to the actualities, the reasons of the abnormal heat were analyzed from such aspects as environmental and filling medium influence. A series of analytical tests were made on the terminals filled with two different kinds of silicone oil, which proved that the problem was caused by inferior silicon oil used as the insulating medium for the terminals. The problem can be solved by replacing the silicon oil.
机构地区 广州供电局
出处 《广东电力》 2007年第9期40-42,共3页 Guangdong Electric Power
关键词 电缆终端 异常发热 绝缘介质 介质损耗 cable terminal abnormal heat insulating medium dielectric loss
  • 相关文献

参考文献3

  • 1DL/T664-1999.带电设备红外诊断技术应用导则[S].[S].,.. 被引量:32
  • 2陈永辉等编著..供电设备红外诊断技术[M].北京:中国水利水电出版社,2006:174.
  • 3长沙电缆附件有限公司.110kV套管式终端发热研究试验报告[R].长沙:长沙电缆附件有限公司,2006. 被引量:1

共引文献31

同被引文献61

引证文献7

二级引证文献45

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部