期刊文献+

同塔并架多回输电线无线电干扰分析 被引量:6

Analysis of the Radio Interference for Parallel Multi-circuit Transmission Lines on the Same Tower
下载PDF
导出
摘要 针对同塔并架多回输电线路的特点 ,讨论了导线相序排列对导线表面场强的影响。并比较四回输电线路三种杆塔的合理选择 ,计算了典型排列方式导体表面场强及同塔并架多回线无线电干扰 ,结果表明各相导线的逆序排列可改善线路两面的干扰状况 。 According to the characteristic of multi circuit transmission lines, this paper discusses the impaction of different wire arrange on the wire surface electric field strength, and finds the best one in three kinds of poles with four circuit transmission lines. This paper calculates the electric field strength of wire surface and the radio interference, and the result indicates that wires contrary arrange can improve the radio interference at two sides and save the land resource.
出处 《高电压技术》 EI CAS CSCD 北大核心 2004年第1期36-38,共3页 High Voltage Engineering
关键词 同塔并架多回输电线路 无线电干扰 电力线路 架空线路 parallel lines on same tower four circuit transmission radio interference