期刊文献+

受压加肋焊接空心球节点抗火试验研究

Experimental study on stiffened welded hollow spherical joints subjected to compression and fire
原文传递
导出
摘要 为研究火灾下受压加肋焊接空心球节点的性能,对2个足尺节点进行受火试验。通过试验得到了加肋焊接空心球节点在标准火灾下的节点表面温度场、不同荷载下节点的耐火时间、破坏形式以及位移特征。根据欧洲规范,建立了三维加肋焊接空心球节点的有限元模型,分析了火灾下节点温度发展规律及位移特征。有限元分析结果与试验结果的对比验证了有限元分析的正确性。研究结果表明:升温过程中,加肋焊接空心球节点中远离加劲肋处的球壳温度最高,靠近加劲肋以及钢管连接处的球壳温度较低;火灾下受压加肋焊接空心球节点的破坏具有突然性,破坏发生在钢管与球节点的连接处;荷载比大的球节点耐火时间短。 In order to study the performance of the stiffened welded hollow spherical joints subjected to compression under fire,tests were conducted on two full-scale specimens. The temperature field of hollow sphere,the ultimate fire resistant duration under different load ratios,failure mode and the displacement characteristics of the joint were obtained. According to the Eurocode,a three-dimensional finite element model of stiffened welded hollow spherical joint was established,and the temperature development and displacement characteristics of the joints were analyzed. The finite element analysis result was compared with the test result to verify the accuracy of finite element analysis. The results show that during the heating process,the highest temperature appears at the hollow sphere where is away from the stiffener. The temperature of hollow sphere near the stiffener and the connection between the sphere and the steel pipe is lower. The failure of the stiffened welded hollow spherical joints under fire and pressure is sudden. The damage occurs at the junction of the steel pipe and the joint. The fire resistant duration of the joint with large load ratio is shorter.
作者 黄炳生 张冉阳 杨放 黄泰杰 张益伟 张旭 操岳飞 HUANG Bingsheng;ZHANG Ranyang;YANG Fang;HUANG Taijie;ZHANG Yiwei;ZHANG Xu;CAO Yuefei;(College of Civil Engineering,Nanjing Tech University,Nanjing 211816,China;Nanjing Gongda Construction Technology Co. Ltd.,Nanjing 210009,China)
出处 《建筑结构学报》 EI CAS CSCD 北大核心 2018年第S1期192-197,共6页 Journal of Building Structures
基金 国家自然科学基金项目(51378259)
关键词 加肋焊接空心球节点 火灾 瞬态试验 温度场 耐火时间 stiffened welded hollow spherical joint fire transient-state test temperature field ultimate fire resistant duration
  • 相关文献

参考文献3

二级参考文献15

  • 1王小蓉.钢结构抗火分析与计算[D].哈尔滨:哈尔滨工程大学,2006,8:1-12. 被引量:3
  • 2ZHANG Y G, XUE S D, YANG Q S, et al. Large- Span Space Structure[M]. Beijing: Mechanical Industry Press, 2005: 1-59. 被引量:1
  • 3WANG R. Analysis and Calculation on Fire Resistance of Steel Structure[D]. Harbin: Harbin Engineering U- niversity, 2006: 1-12. 被引量:1
  • 4LI G Q, JIANG S C, LING X. Computation and Design of Steel Structure in Fire[M]. Construction Press of China, 2000: 1-50. 被引量:1
  • 5International Standard ISO834. Fire-Resistance Tests Elements of Building Construction, Amendment 1, A- mendment 2[S], 1980. 被引量:1
  • 6LI G Q, HAN L H, LOU G B, et al. Fire-Resistant Design of Steel Structure and Steel-Concrete Compound Structure[M]. Construction Press of China, 2006: 13-50. 被引量:1
  • 7European Committee for Standardization. ENV 1993-1- 2, Eurocode 3, Design of Steel Structures, Part 1. 2: Structural Fire Design[S]. 1993. 被引量:1
  • 8European Committee for Standardization. ENV 1993-1-2, Eurocode 4, Design of Composite and Structures, Part 1.2: Structural Fire Design[S], 1994. 被引量:1
  • 9ISO 834 Fire-resistance tests elements of building construction: amendment 1, amendment 2 [S]. 1980. 被引量:1
  • 10李目强,韩林海,楼国彪,等.钢结构及钢-混凝土组合结构抗火设计[M].北京:中国建筑工业出版社,2006. 被引量:1

共引文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部