摘要
结合A—B法与生物接触氧化法的优点,试验证明该工艺合理可行。A段吸附池在兼性条件下,当HRT=0.5h时,COD_(er)去除率为50%左右;在好氧条件下当HBT=1.5h时,B段COD_(er)的去除率为60%左右。系统COD_(er)总去除率在80%左右。
A-B method and bio - contact - oxidation process combination are very useful to treat domestic wastewater. In part A CODcrwas removed about 50% at HRT = 0.5h and DO = 0.5mg/L, in part B about 60% at HRT=1.5h and DO≥2mg/L. This system removal rate of CODcr were 80% totally.
出处
《净水技术》
CAS
2002年第4期26-28,共3页
Water Purification Technology
基金
山东省水利厅立项项目