期刊文献+

基于M序列的磁电法探测坝基渗漏试验研究

Experimental Study on Dam Foundation Leakage Detection by Magnetoelectric Method Based on M Sequence
下载PDF
导出
摘要 坝基渗漏问题是影响水库大坝整体安全的关键因素.为有效、准确探测坝基渗漏,基于伪随机辨识原理,将M序列相关辨识的磁电法技术应用于堤坝渗漏探测.首先,通过物理模型试验分析,获取不同渗漏深度下的磁感应强度分布、均方差及变异系数特征;然后,设计不同渗漏形态、高阻屏蔽层及渗漏通道数量条件,获取探测结果对倾斜通道、高阻屏蔽层以及多条渗漏通道的响应特征;最后,通过云南红石岩堰塞坝现场试验,分析该技术的可行性.试验结果表明:在不同埋深条件下,磁感应强度最大值的变异系数均控制在2%以内;渗漏通道的倾斜引起磁感应强度沿渗漏方向缓慢降低,其磁场等值线图的脊线反映倾斜渗漏方向;高阻屏蔽层仅对磁感应强度产生影响,磁感应强度误差在10%~20%;多组渗漏通道会反映在磁场等值线图中异常场的多处集中分布;现场试验探测的渗流流向分别为NW300°、SW265°、W215°和NW305°. The dam foundation leakage problem has been a key factor affecting the overall safety of reservoir dams.To effectively and accurately detect dam foundation leakage,the magnetoelectric method based on M sequence correlation identification technology was applied to the dam leakage detection based on the pseudorandom identification principle.Firstly,the distribution of magnetic induction intensity,mean square error,and variation coefficient under various leakage depth conditions were characterized through the analysis of physical model experiments.Then,various leakage forms,high-resistance shielding layers,and leakage channel numbers were designed,so as to obtain the response characteristics of the detection results to the inclined channel,highresistance shielding layer,and multiple leakage channels.Finally,the field test of Hongshiyan Dam in Yunnan Province was conducted to study the feasibility of this technology.The results show that under different burial depth conditions,the variation coefficients of maximum magnetic induction intensity vary within 2%.Along the inclined leakage channel,the magnetic induction intensity decreases slowly,and the ridge direction of the magnetic field contour map can be considered as the inclined leakage direction.The magnetic induction intensity is affected by the high-resistance shielding layer and has an error between 10%and 20%.The multiple leakage channels can be reflected by the concentrative distribution of abnormal zones in magnetic field contour maps.The leakage directions are observed in the field test,containing NW300°,SW265°,W215°,and NW305°,respectively.
作者 刘瑾 车文越 钱卫 张化鹏 黄国娇 丁亮 何秀凤 LIU Jin;CHE Wenyue;QIAN Wei;ZHANG Huapeng;HUANG Guojiao;DING Liang;HE Xiufeng(School of Earth Sciences and Engineering,Hohai University,Nanjing 211100,China;Department of Physics,University of Toronto,Toronto ON M5S 1A7,Canada)
出处 《西南交通大学学报》 EI CSCD 北大核心 2024年第6期1448-1456,共9页 Journal of Southwest Jiaotong University
基金 国家重点研发计划(2018YFC1508501)。
关键词 渗漏识别 M序列 磁电法 坝基渗漏 土槽试验 leakage identification M sequence magnetoelectric method dam foundation leakage soil bin test
  • 相关文献

参考文献15

二级参考文献121

共引文献108

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部