摘要 空气源热泵直接地板辐射供暖系统以制冷剂为热媒直接加热地板,具有系统简单、传热效果好的优点。文中搭建空气源热泵直接地板辐射供暖实验装置,在0℃、-5℃和-10℃3种不同室外环境温度下,对毛细管地板辐射末端供暖升温过程进行实验研究。实验结果表明:室外温度为-5℃时,地板温度稳定基本需要120 min,同一根毛细管壁制冷剂蒸气入口端与出口端温差较小为1.55℃,而在20 mm厚水泥地板表面上其温差为1.73℃;室外温度为-10℃时,地板升温速度最慢为0.15℃/min,小室内空气升温速度为0.09℃/min,此时机组制热COP稳定在3.06。 The air source heat pump direct floor radiant heating system directly heats the floor with refrigerant as the heat medium,which has the advantages of simple system and good heat transfer effect.An experimental device of capillary floor radiant heating with air source heat pump was built,and the heating process experiment of capillary floor radiant was carried out at different outdoor ambient temperatures.The experimental results show that when the outdoor temperature is-5℃,it takes about 120 minutes for the floor temperature to stabilize.The temperature difference between the refrigerant vapor inlet and outlet ends of the same capillary wall is relatively small at 1.55℃,while on the surface of a 20mm thick cement floor,the temperature difference is 1.73℃.When the outdoor ambient temperature is-10℃,the floor heating rate is the slowest at 1.5℃/10 min,and the indoor air heating rate is 0.9℃/10 min.At this time,the heating COP of the system is stable at 3.06.
作者 牛建会 王海超 吕天舒 安泽龙 NIU Jianhui;WANG Haichao;LV Tianshu;AN Zelong(Department of Energy Engineering,Hebei University of Architecture,075000,Zhangjiakou,Hebei,China)
出处 《河北水利电力学院学报》 2024年第3期61-67,共7页 Journal of Hebei University Of Water Resources And Electric Engineering
基金 河北建筑工程学院博士科研启动基金项目(B-202303) 河北建筑工程学院研究生创新基金项目(XY2023052)。
关键词 空气源热泵 毛细管 直接地板辐射 升温过程 air source heat pump capillary direct floor radiation heating process
  • 相关文献

参考文献20

二级参考文献111

共引文献127

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部