期刊文献+

基于空气洁净技术的通信机房通风降温系统适应性及节能潜力探讨

Exploration of the adaptability and energy-saving potential of communication room ventilation and cooling system based on air purification technology
下载PDF
导出
摘要 通过分析通信机房的特点及空调能耗现状,提出一种基于空气洁净技术的通风降温系统。以青岛市某通信机房为例,实地测试该机房应用通风降温系统后的室内空气洁净度,利用DeST软件对该机房的能耗状况进行定量模拟分析,计算该机房应用通风降温系统后的全年节能率,并对5个气候区的典型城市进行计算,探讨通风降温系统在全国五大建筑热工分区的节能潜力。结果表明,应用通风降温系统后,青岛某机房的节能率为64.95%,通风降温系统在全国不同热工分区的模拟节能率为33.37%~73.7%,在通信机房中应用通风降温系统的节能效果十分显著。 By analyzing the characteristics of communication rooms and the current state of air conditioning energy consumption,a ventilation and cooling system based on air purification technology is proposed.Taking a communication room in Qingdao as an example,the indoor air cleanliness after the application of the ventilation and cooling system is tested on-site.The energy consumption of the room is quantitatively simulated and analyzed using the DeST software,and the annual energy saving rate after the application of the ventilation and cooling system is calculated.Calculations are also conducted for typical cities in five climatic zones to explore the energy-saving potential of the ventilation and cooling system in the five major building thermal zones across the country.The results show that after applying the ventilation and cooling system,the energy saving rate of a certain room in Qingdao is 64.95%,and the simulated energy saving rate of the ventilation and cooling system nationwide is between 33.37% and 73.7%.The energy-saving effect of applying the ventilation and cooling system in communication rooms is very significant.
作者 赵敖 李春辉 周希刚 栾书敏 李振海 ZHAO Ao;LI Chun-hui;ZHOU Xi-gang;LUAN Shu-min;LI Zhen-hai
出处 《节能》 2024年第7期6-10,共5页 Energy Conservation
关键词 通信机房 通风降温系统 节能潜力 communication room ventilation and cooling system energy-saving potential
  • 相关文献

参考文献9

二级参考文献71

共引文献45

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部