合肥市22家公共场所集中空调通风系统卫生状况 被引量:2

Analysis of health status of central air conditioning ventilation system in 22 public places in Hefei City
原文传递
导出
摘要 目的通过分析公共场所集中空调通风系统抽检结果,探讨影响集中空调通风系统合格率的因素。方法随机抽取合肥市22个使用集中空调通风系统的公共场所,检测空调送风中可吸入颗粒物(PM_(10))、细菌总数、真菌总数、新风量、风管内表面细菌总数、风管内表面真菌总数、空调风管内表面积尘量、冷却水及冷凝水嗜肺军团菌。检测及评价依据《公共场所集中空调通风系统卫生规范》(WS394—2012)。结果检测22家公共场所,总合格率为77.27%,其中17家场所检测指标合格率100.00%。13家宾馆酒店,10家合格,合格率为76.90%,其他场所合格率为77.78%,差异无统计学意义(P_(Fisher)=1.000)。空调送风中真菌总数合格率最低,为77.27%,其次为空调送风中细菌总数,合格率为81.82%,空调风管内表面细菌总数及真菌总数合格率均为95.45%,其余指标合格率均为100.00%。结论合肥市集中空调通风系统抽检合格率不容乐观,空调送风微生物污染是影响合格率的主要因素。 Objective To tem explore sampling the results influencing of factors air of the qualification rate system randomly of central in air-conditioning ventilation syspublic particulate duct,total places.Methods 22detect by places analyzing using the central central ventilation conditioning system ventilation were public selected air conditioning bacteria,total in Hefei volume,total to the the inhalable surface matter number water(PM),total of fungi,fresh surface air duct,dust evaluation number the of surface“hygienic no bacteria of on inner of air fungi on condensate the inner of air and amount based on on air code duct,Legionella for pneumophila Conditioning in and cooling Ventila-and System testing water.Detection the Central significant Air394—2012).Results was tion in indicators Public Places”hotels(WS other statistically total difference the in the conditioner supply qualified supply rate air of had qualified((P_(Fisher)=in qualified and places1.000).The total number bacteria of the on fungi air in air the rate were lowest of rate of77.27%,followed qualified by total the number of of bacteria in fungi conditioner inner air air with a81.82%.The95.45%,and rates of rates the of number other and the surface of the qualified conditioning rate duct100.00%.Conclusion The is the air qualified conditioning affecting the ventilation indicators system were Hefei of of sampling air insupply spection the of main central factor in not optimistic,and the microbial pollution is the qualified rate.
作者 耿志 孙露 GENG Zhi;SUN Lu(Institute of Comprehensive Law Enforcement and Supervision,Hefei Municipal Health Commission,Anhui 230092,China)
出处 《安徽预防医学杂志》 2022年第3期212-214,233,共4页 Anhui Journal of Preventive Medicine
关键词 公共场所 集中空调通风系统 检测 合格率 Public places Central air conditioning ventilation system Detection Qualified rate
  • 相关文献

参考文献13

二级参考文献112

共引文献63

同被引文献16

引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部