摘要 为确定临时高压消防给水系统中稳压泵的设计流量和流量开关的设定值,对稳压系统在火灾发生时和火灾未发生时的工作状态进行分析,并重点考察了P_(s1)、P_(s2)控制点对应的流量与管网正常泄漏量、水灭火设施出水量、气压罐出水量、气压罐充水量之间的关系。分析表明:通过对稳压装置在火灾发生时和火灾未发生时的工作状态进行分析,来确定稳压泵设计流量和流量开关设定值的范围,然后利用取中间值的方法计算出稳压泵的设计流量和流量开关的设定值。另外,通过将消防泵在接到流量开关报警信息后延迟10 s启动来防止流量开关的设定值可能会小于等于稳压泵启动运行瞬间流量,进而避免误报警。 In order to determine the design flow of stabilized pressure pump and setting value of flow switch within the temporary high-pressure fire water system,this paper analyses the working condition of the fire pressure stabilizing system in case of fire and not in fire,emphatically investigating the relationship between the corresponding flow rate of P_(s1)&P_(s2) and the normal leakage rate of network pipe,fire water supply facilities,hydraulic discharge of air pressure tank,and make-up water of air pressure tank.The analysis shows that the range of the design flow rate of fire pressure stabilizing system and the setting value of the flow switch can be determined by analyzing the working state of the stabilized pressure system in case of fire and not in fire,and the median value shall be taken when it caculates the data of the design flow of stabilized pressure pump and the setting value of flow switch.Moreover,due to the set value of the flow switch may be less than or equal to the flow at the start of the stabilized pressure pump,we can delay the start of the fire pump for 10 seconds after receiving the alarm information of the flow switch,so as to avoid the false alarm.
作者 王琪 许文建 洪礼刚 WANG Qi;XU Wenjian;HONG Ligang(Grace Fluid Technology Co.,Ltd.,Suzhou 215127,China)
出处 《给水排水》 CSCD 北大核心 2022年第6期110-113,共4页 Water & Wastewater Engineering
关键词 稳压装置 泄漏量 出水量 稳压泵流量设计 流量开关设定值 延迟 Fire pressure stabilizing system Leakage rate Hydraulic discharge Design flow of stabilized pressure pump Setting value of flow switch Delay
  • 相关文献

参考文献4

二级参考文献17

  • 1何芳,刘遂庆.供水管网爆管事故分析与对策探讨[J].管道技术与设备,2004(5):20-23. 被引量:54
  • 2Goodwin S J. The Results of the Experimental Program on Leakage and Leakage Control. Water Research Center, 1980, (52):TR154. 被引量:1
  • 3Hiki S. Relationship between Leakage and Pressure. Journal of Japan Waterworks Association, 1982, (5):50--54. 被引量:1
  • 4Tucciarelli T, Criminisi A, Termini D. Leak Analysis in Pipeline Systems by Means of Optimal Valve Regulation. Journal of Hydraulic Engineering, 1999, (3) :277 -- 285. 被引量:1
  • 5Germanopoulos G. A Technical Note in the Inclusion of Pressure Dependent Demand and Leakage Terms in Water supply Network Models. Civil Engineering Systems, 1985, (2) : 171 -- 179. 被引量:1
  • 6Germanopoulos G, Jowitt P W. Leakage reduction by excessive pressure minimization in a water supply network. Proc, Institution Civ Engrs, Part 2, 1987:195--214. 被引量:1
  • 7Lasey K,Mays L W,Tung Y K.Reliability and availability analysis of water distribution systims.Urban Water,2001,(3):253-260. 被引量:1
  • 8Le Gat Y,Eisenbeis P.Using maintenance records to forecast failuresin water networks.Urban Water,2000,(2):173-181. 被引量:1
  • 9Pelletier G,Mailhot A,Villeneuve J P.Modeling water pipe breaksthree case studies.Water Resources Planning and Management,2003,(3/4):115-123. 被引量:1
  • 10Dusan O.Modelling of demand and losses in real-life water distribution systems.Urban Water,2000,(2):131-139. 被引量:1