摘要
分析了变压器励磁涌流及因其产生的和应涌流,电压跌落等问题对供配电系统稳定运行的影响,基于剩磁计算原理的涌流抑制技术和传统基于固定角度分合闸进行涌流抑制产品的区别,及采用该技术在海上设施完美解决三相联动操动机构AIS及GIS断路器回路变压器涌流和电压跌落问题的实例。
The influence on power transmission and distribution system by transformer inrush current,and concomitant sympathetic inrush current,voltage dip is analyzed.It then discussed the difference between inrush current restrain base on residual flux calculation method and traditional fix angle switching method,In the end,it shows the excellent result the technology used in offshore facilities that equipped with gang-operated AIS & GIS circuit breakers.
作者
黄浩军
HUANG Haojun(CNOOC(China)Co.,Ltd.,Tianjin Branch,Tianjin 300452,China)
出处
《电气应用》
2022年第3期87-96,共10页
Electrotechnical Application
关键词
励磁涌流
变压器涌流抑制
剩磁计算
三相联动断路器
相控断路器
magnetizing inrush current
transformer inrush current restrain
residual flux calculation
gang-operated circuit breaker