摘要 针对多联式空调(热泵)机组室内机之间制冷剂分流均匀性进行试验,结果表明,高/中压比值是影响分流的一个主要因素。调整控制参数后再次进行测试发现,高/中压比小于1.5,中/低压比大于1.9时,室内机之间制冷剂分流良好,但各电子膨胀阀的开度差别较大;使用分流器代替分流管后,对应的电子膨胀阀开度差别在37步以内,进一步提高了室内机之间制冷剂分流的均匀性。 The refrigerant flow distribution uniformity between each indoor unit of multi-connected air-conditioning(heat pump)unit is studied by test.The results show that the high/intermediate pressure ratio is one of the key factors influencing the flow distribution.The tests are conducted after adjusting the control parameters,it shows that the flow distribution behaves better when the high/intermediate pressure ratio is less than 1.5 and the intermediate/low pressure ratio is higher than 1.9,while the difference between each electronic expansion valve opening degrees is large.After using shunt instead of shunt tube,the difference is within 37,which greatly improves the flow distribution uniformity of indoor units.
作者 卜康太 樊华云 王思偲 肖彪 何林 Bu Kangtai;Fan Huayun;Wang Sisi;Xiao Biao;He Lin(State Key Laboratory of Air Conditioning Equipment and System Energy Conservation,Gree Electric Appliances,Inc.of Zhuhai)
出处 《制冷与空调》 2022年第1期15-19,共5页 Refrigeration and Air-Conditioning
关键词 多联式空调(热泵)机组 三缸双级压缩 变频 变容 分流 电子膨胀阀 中间压力 multi-connected air-conditioning(heat punp)unit three-cylinder two-stage compression variable frequency variable capacity flow distribution electronic expansion valve intermediate pressure
  • 相关文献

参考文献3

二级参考文献33

  • 1王森,石文星,田长青.双级压缩变频空气源热泵的试验研究[J].流体机械,2003,31(z1):38-42. 被引量:7
  • 2马最良,姚杨,姜益强.暖通空调热泵技术[M].北京:中国建筑工业出版社,2008 被引量:30
  • 3Y C Park, Y C Kim, M K Min. Performance analysis on a multi-type inverter air conditioner [J]. Energy Conversion and Management (S0196-8904), 2001, 42: 1607-1621. 被引量:1
  • 4J M Choi, Y C Kim. Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves [J]. Energy (S1751-4223), 2003, 28: 141-55. 被引量:1
  • 5W Shi, S Shao, X Li, X Peng, X Yang. A network model to simulate performance of variable refrigerant volume refrigeration systems [J]. Amer. Soc. Heating, Ref. Air-Conditoning Eng (S0001-2505). Inc., Kansas City, MO, United States, 2003: 61-68. 被引量:1
  • 6S Shao, W Shi, X Li, Q Yan. Simulation model for complex refrigeration systems based on two-phase fluid network-Part I: Model development [J]. International Journal of Refrigeration (S0140-7007), 2008, 31: 490-9. 被引量:1
  • 7W Shi, S Shao, X Li, Q Yan. Simulation model for complex refrigeration systems based on two-phase fluid network - Part II: Model application [J]. International Journal of Refrigeration (S0140-7007), 2008, 31: 500-9. 被引量:1
  • 8C Wu, Z Xingxi, D Shiming. Development of control method and dynamic model for multi-evaporator air conditioners (MEAC) [J]. Energy Conversion and Management (S0196-8904), 2005, 46:451-465. 被引量:1
  • 9R Shah, A G Alleyne, C W Bullard. Dynamic modeling and control of multi-evaporator air-conditioning systems (S0001-2505). [M]. Atlanta, GA 30329, United States, Anaheim, CA, United States: Amer. Soc. Heating, Ref. Air-Conditoning Eng Inc., 2004:111-121. 被引量:1
  • 10S-C Hu, R-H Yang. Development and testing of a multi-type air conditioner without using AC inverters [J]. Energy Conversion and Management (S0196-8904), 2005, 46: 373-383. 被引量:1

共引文献23

同被引文献5

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部