摘要 介绍了一起35 kV变压器内部绝缘故障分析及处理案例。油色谱检测发现变压器内部存在低能放电,吊芯发现绕组引线和有载分接开关静触头接线柱间存在击穿痕迹。对此类故障进行了分析和总结,为今后变压器运维积累了经验。 In this paper,an analysis and treatment case of internal insulation fault in 35 kV transformer is introduced.The oil chromatographic test data shows that there is low-energy discharge in the transformer,and through the inspection of hanging cover,it is found that there is a breakdown trace between the winding lead and the static contact terminal of on-load tap changer.This kind of defects is analyzed and summarized,it accumulates experience for transformer operation and maintenance and technical supervision in the future.
作者 刘浩 张润峰 李健 刘佳亮 肖雄 Liu Hao;Zhang Run-feng;Li Jiang;Liu Jia-liang;Xiao Xiong
出处 《电力系统装备》 2021年第23期111-112,共2页 Electric Power System Equipment
关键词 变压器 绝缘故障 油色谱 故障诊断 transformer insulation defect oil chromatographic fault diagnosis