摘要
主要对某高校现代化实验室通风空调系统的设计进行了研究。实验楼排风系统、新风系统均采用变风量系统,控制策略采用余风量控制法以维持实验室排风量和新风量动态平衡。实验室空调采用风机盘管加新风系统。根据实验室同时使用系数,减少风冷热泵冷水的配置容量,以减少初投资。
The study focuses on the design of ventilation and air conditioning system in a modern laboratory in a university.The exhaust system and fresh air system of the building adopt variable air volume system.The control strategy uses the residual air volume control method to maintain the dynamic balance between exhaust and fresh air volume in the building.the fan coils and fresh air system are used by the laboratories,The configuration capacity of air-cooled heat pump water chiller as well as initial investment can be reduced based on the laboratory's simultaneous use factor.
出处
《洁净与空调技术》
2021年第4期63-66,共4页
Contamination Control & Air-Conditioning Technology
关键词
实验室
通风柜
变风量通风系统
空调系统
余风量控制
Laboratory
Fume hood
Variable air volume ventilation system
Air conditioning system
Residual air volume control