摘要
针对高校寒假时段不使用的特点,依据现有规范中不保证天数的思想,提出高校建筑采暖室外计算温度的取值方法,并给出不保证五天、不保证四天、不保证三天的采暖室外计算温度值,供设计单位参考。统计结果表明:各地的高校建筑采暖室外计算温度均有所提高,最多可提高1.5℃,采暖设计热负荷最大可降低5.1%左右。
In view of the characteristics of not being used during the winter vacation in colleges and universities,according to the idea of not guaranteeing the number of days in the existing norms, this paper puts forward the value method of heating outdoor calculation temperature in colleges and universities, and gives the heating outdoor calculation temperature value of not guaranteeing five days, not guaranteeing four days, not guaranteeing three days, for the reference of design units. The statistical results show that the heating outdoor calculation temperature of university buildings in different places has been increased by 1.5 ℃ at most, and the design heating load can be reduced by 5.1% at most.
作者
杨黎黎
齐尚榕
任永忠
YANG Li-li;QI Shang-rong;REN Yong-zhong(College of Civil Engineering,Lanzhou Institute of Technology;Gansu Institute of Urban Planning and Design Co.,Ltd.)
出处
《建筑热能通风空调》
2021年第8期67-69,98,共4页
Building Energy & Environment
基金
兰州工业学院“启智”人才培养计划基金(2019QZ-05)
兰州工业学院校级岩土工程重点学科(2019XK-04)
甘肃省高等学校创新能力提升项目(2019B-180)。
关键词
高校建筑
采暖室外计算温度
不保证天数
university building
heating outdoor calculation temperature
unguaranteed days