期刊文献+

Evaluating the improvement effect of low-energy strategies on the summer indoor thermal environment and cooling energy consumption in a library building:A case study in a hot-humid and less-windy city of China 被引量:5

原文传递
导出
摘要 Public buildings such as libraries consume a vast amount of cooling energy for maintaining a comfortable and stable indoor environment in summer,especially in the hot-humid climate.This study used a case study approach to discuss the effect of low-energy strategies that can be applied to improve indoor thermal environment and cooling energy consumption of library buildings in hot and humid cities like Nanning City(a southern city,China).The use of cooling window shutters(a shutter with the effects of shading and evaporative cooling)and ceiling fans for generating airflow was considered as applicable energy-saving measures in this study,and a university library was selected as the study building in which the two energy-saving measures were employed.The SET*and annual cooling load before and after the adoption of the proposed measures were quantitatively investigated with a building energy consumption simulation software(DesignBuilder).Simulation results showed that the daytime SET*values can be reduced by 3.0℃and 4.5℃respectively on a typical summer day after the use of the cooling shutters and ceiling fans.Moreover,the cooling loads can also be decreased by 8.4%and 16.6%respectively.Particularly,the combination of these two measures enabled the daytime SET*value and annual cooling load lower by 7.0℃and 60.8%respectively.
出处 《Building Simulation》 SCIE EI CSCD 2021年第5期1423-1437,共15页 建筑模拟(英文)
基金 supported from the National Natural Science Foundation of China(No.51968003) the Guangxi Science and Technology Project(No.AB16380193).
  • 相关文献

参考文献2

二级参考文献30

  • 1de Dear R J. A global database o{ thermal comfort field experiments[G]//ASHRAE Trans, 1998, 104 (1). 1141-1152. 被引量:1
  • 2de Dear R J, Brager G S. Developing an adaptive model of thermal comfort and preference [G]. //ASHRAE Trans, 1998, 104 (1): 145-167. 被引量:1
  • 3Wyon D P. Methodology for indoor environmental research[G]//The ICIE Symposium, 2001. 被引量:1
  • 4ISO International Standard 7726 Ergonomics of the thermal environment--Instruments for measuring physical quantities[S]. Geneva: ISO, 1998. 被引量:1
  • 5Mclntyre D A. Indoor climate[M].London: Applied Science Publishers Ltd, 1980. 被引量:1
  • 6Fanger P O, Toftum J. Thermal comfort in the future--Excellence and expectation[C] // Conference Proceedings on Moving Thermal Comfort Standards into 21st Century, Windsor, UK, 2001. 被引量:1
  • 7Wong N H, Khoo S S. Thermal comfort in classrooms in the tropics[J]. Energy and Buildings,2003, 35 (4): 337-351. 被引量:1
  • 8Zhang G, Zheng C, Yang W, et al. Thermal comfort investigation of naturally ventilated classrooms in a subtropical region[J]. Indoor and Built Environment, 2007, 16 (2): 148-158. 被引量:1
  • 9Zhang Y, Zhao R. Relationship between thermal sensation and comfort in non-uniform and dynamic environments[J]. Building and Environment, 2009, 44 (7): 1386-1391. 被引量:1
  • 10Zhang Y, Zhao R. Overall thermal sensation, acceptability and comfort [ J ]. Building and Environment, 2008, 43 (1): 44-50. 被引量:1