10kV配电站备自投装置误动问题分析

Analysis on Misoperation of Backup Automatic Switching Device in 10 kV Distribution Station
下载PDF
导出
摘要 配电网的运行状态直接影响着供电可靠性,而10 kV备自投装置能否准确动作是关键。针对一个10 kV配电站备自投装置误合分段断路器的案例,分析备自投动作逻辑,总结事故发生的原因,最后基于分析结论提出了防范措施。 The operating state of the distribution network directly affects the reliability of the power supply.Whether the 10 kV backup automatic switching equipment can accurately operate is the key point.Aiming at a case of a 10 kV substation′s backup automatic switching device wrongly closing the section breaker,the action logic of standby automatic switch was analyzed and the causes of the accident was summarized.Finally,based on the analysis conclusion,the preventive measures were put forward.
作者 郑天奇 徐迅 杨剑 史媛 ZHENG Tianqi;XU Xun;YANG Jian;SHI Yuan(Shibei Electric Power Supply Company,State Grid Shanghai Power Company,Shanghai 200072,China)
出处 《电工技术》 2021年第3期52-54,共3页 Electric Engineering
基金 国家电网公司科技项目资助(编号52091418005N)。
关键词 配电站 备自投装置 合闸回路 distribution station backup automatic switching equipment closing circuit