某抽水蓄能电站主变压器低压闭锁过流保护动作原因分析及改造方案 被引量:1

Analysis on the Cause of Overcurrent Protection Action of Low-voltage Lockout in a Main Transformer of Pumped-storage Hydroelectricity and Its Improvement Scheme
下载PDF
导出
摘要 本文对某抽水蓄能电站主变压器复合低压闭锁过流保护动作原因进行了详细的分析。该保护装置采取冗余配置,两套保护装置中复合低压闭锁过流保护采用的电压量为主变压器高压侧同一电压互感器的不同绕组,针对本次保护动作暴露的缺陷,通过对比两套保护装置采集到的电压量是否同时消失,判别是否对该保护出口进行闭锁,从而使该保护动作的正确率进一步提高,最终实现对主变压器及机组保护TV断线功能进行完善。使该保护在高压侧一次主接线电压降低并满足过流条件时正确动作,而非在电压互感器二次回路断开并满足过流条件时误动作。 In this paper,a detailed analysis of the main transformer of a pumped storage power station compound low voltage block overcurrent protection action reasons.The protection device to take redundant configuration,two sets of protective device in the composite low voltage lockout overcurrent protection mainly voltage transformer high voltage side of the same different winding of voltage transformer,the purpose of this article is aimed at the protection action exposed defects,by comparing the two sets of protective device to voltage whether disappear at the same time,judging whether the protection of export is blocking,so that the accuracy of protection operation to further improve,finally realizes the protection of the main transformer and the unit PT disconnection functions are perfect.Make the protection work correctly when the primary wiring voltage of the high voltage side is reduced and the overcurrent condition is met,rather than work wrongly when the secondary circuit of the voltage transformer is disconnected and the overcurrent condition is met.
作者 宋泽超 张浩 刘勇 胡峰超 SONG Zechao;ZHANG Hao;LIU Yong;HU Fengchao(Shanxi Xilongchi Pumped Storage Power Station Co.Ltd.,Xinzhou 034000,China)
出处 《水电与抽水蓄能》 2021年第1期49-52,共4页 Hydropower and Pumped Storage
关键词 主变压器复合低压闭锁过流保护 TV二次侧短路 TV断线闭锁保护 main transformer composite low-voltage blocking overcurrent protection TV secondary side short circuit TV broken line blocking protection
  • 相关文献

参考文献6

二级参考文献8

共引文献4

同被引文献19

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部