期刊文献+

多层地铁车站结构性能试验研究 被引量:13

Performance Experiment of a Multistory Subway Station
下载PDF
导出
摘要 为掌握地震作用下多层地铁车站结构从材料、局部构件到整体结构的非线性破坏状态,以上海市某多层地铁车站工程为背景,开展了1:10大型静力推覆(Pushover)试验。结合地下结构地震响应特征,采用倒三角分布的侧向位移推覆加载模式,并由多个作动器实现多点协调加载。分析研究了多层地铁车站结构的裂缝开展过程、结构及构件破坏形态、塑性铰开展顺序、Pushover曲线,并总结了结构整体和中柱的破坏模式,给出车站结构重要性能点数值,综合评价了多层地铁车站结构的抗震性能及特点,可为基于性能的抗震设计提供依据。 In order to study the non-linear failure state of materials,local components and integral structure of multistory subway station under earthquake action,a 1:10 large-scale pushover test was carried out in the background of a multi-story subway station project in Shanghai.According to the seismic response characteristics of underground structures,loading mode was in the form of inverted triangular displacement carried out by means of multi-point coordinated loading by three actuators.Development process of cracks,plastic hinges formation sequence and pushover curve were studied.Failure patterns and modes of the whole structure and central columns were contrasted.Critical performance data points of the structure was given.On account of the pushover test results,the seismic performance of deep metro station structure was also comprehensively analyzed,which can provide reference for designs of similar structure based on seismic performance.
作者 陈之毅 刘文博 陈炜 CHEN Zhiyi;LIU Wenbo;CHEN Wei(College of Civil Engineering,Tongji University,Shanghai 200092,China;State Key Laboratory of Disaster Reduction in Civil Engineering,Tongji University,Shanghai 200092,China;Shanghai Municipal Engineering Design Institute(Group)Co.Ltd.,Shanghai 200092,China)
出处 《同济大学学报(自然科学版)》 EI CAS CSCD 北大核心 2020年第6期811-820,共10页 Journal of Tongji University:Natural Science
基金 国家自然科学基金(51778464)。
关键词 多层地铁车站 推覆试验 塑性铰 中柱 抗震性能 multi-storey subway station pushover test plastic hinges central columns seismic performance
  • 相关文献

参考文献21

二级参考文献126

共引文献541

同被引文献177

引证文献13

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部