摘要
为研究高压架空线路发生单相接地故障对附近输油输气管道的电磁影响,以220 kV同塔双回架空线路与输油输气管道并列运行为背景,利用电磁暂态仿真软件ATP建立同塔双回输电线路及油气管道等效时域模型,分析了故障点位置、并列运行部分杆塔接地电阻大小、导线高度,管道与杆塔中心线水平间距、管径大小等因素对高压输电线路附近油气管道电磁感应电压的影响。结果表明:油气管道的电磁感应电压受接地点故障位置、杆塔接地电阻以及管道距杆塔中心线水平间距的影响较大;导线高度、管径大小等因素对管道上产生的电磁感应电压影响不明显。得出的结论可以为高压输电线路与输油输气管道同走廊建设提供理论指导。
In order to study the electromagnetic influence due to Single-phase earth fault on the nearbypetroleum/gas pipelines,taking a 220 kV double circuit transmission line on the same tower for example.The time domain simulation calculation model is established by the electromagnetic transient simulationsoftware ATP,Which was used to analyze the effects of fault position,height of transmission line,groundresistance of towers,horizontal spacing,and diameter of pipe for the interference of oil-gas pipeline inthe vicinity of the high voltage transmission line.The results show that electromagnetically induced volt-age of oil and gas pipeline is obviously affected by fault position,ground resistance and horizontal dis-tance,while the lead height and pipeline diameter have little impact on the induced voltage.The conclu-sion can provide theoretical guidance for the laying of gas pipeline in the vicinity of the high voltage line.
作者
黄军
罗日成
史志强
李懿儒
陈湘鹏
谭逢焘
方梦鸽
HUANG Jun;LUO Richeng;SHI Zhiqiang;LI Yiru;CHEN Xiangpeng;TAN Fengtao;FANG Mengge(School of Electrical and Information Engineering,Changsha University of Science&Technology,Changsha 410004,China)
出处
《电瓷避雷器》
CAS
北大核心
2020年第2期26-31,共6页
Insulators and Surge Arresters
基金
国家自然科学基金资助课题(编号:50977003)
电力与交通安全监控及节能技术教育部工程研究中心基金(编号:2010#03)。
关键词
高压输电线路
单相接地
同塔双回
油气管道
电磁影响
ATP-EMTP
high voltage transmission line
single-phase earth fault
double-circuit on the same tower
oil and gas pipeline
electromagnetic effect
ATP-EMTP