摘要
随着集合式电容器的大量使用,集合式电容器故障也逐渐增多。本文针对一起集合式电容器差压保护误动案例,通过一次设备检查、定值计算和差压计算等3个方面进行详细的分析,发现该类型集合式电容器存在差压保护灵敏度不足问题。最后通过采取对电容器保护方式改造、提高保护定值裕度、降低保护误动等措施降低集合式电容器因差压保护灵敏度不足问题而引起的故障。
With the extensive use of the assembled capacitors,the fault of them increases gradually.In view of protective action example of the capacitor,it is found that insufficient differential protection sensitivity is existed in the capacitor throughout detailed analysis from such three aspects as inspection of primary equipment,setting calculation and differential voltage calculation.Finally,such measures as modifying protectionmode,improving the protection setting margin and reducing protection mal-operation are taken so to reduce the fault of the capacitor due to insufficient differential voltage protection sensitivity.
作者
张波
陈水耀
邹晖
周建平
李斌帅
赖尚峰
陈彩霞
ZHANG Bo;CHEN Shuiyao;ZOU Hui;ZHOU Jianping;LI Binshuai;LAI Shangfeng;CHEN Caixia(Maintenance Company of State Gird Zhejiang Electric Power Co.,Ltd.,Hangzhou 311232,China)
出处
《电力电容器与无功补偿》
北大核心
2020年第2期38-41,共4页
Power Capacitor & Reactive Power Compensation
关键词
集合式电容器
差压保护
桥差保护
assembled capacitor
differential protection
bridge differential voltage protection