期刊文献+

±800千伏特高压某换流站电磁环境测试分析 被引量:3

Test and analysis of the electromagnetic environment of ±800kV ultra-high voltage converter station
原文传递
导出
摘要 目的反映±800千伏直流换流站的场界及场内敏感点电磁环境,探究特高压换流站电磁环境的分布规律及影响因素。方法通过对±800千伏换流站的场界及场内敏感点电磁环境进行实测及统计分析。结果±800千伏换流站的最大合成场强小于30 kV/m、工频电场小于4 kV/m、工频磁感应强度小于100μT。结论±800千伏换流站电磁环境水平符合各项标准要求。 Objective To study the distribution of the electromagnetic environment in ultra-high voltage converter station and the influence of electromagnetic radiation generated by a ±800 kV converter station on the environment.Methods The electromagnetic environment of sensitive points and field boundary points in ±800 kV converter station were measured and analyzed.Results The results showed that the maximum synthetic field strength of ±800 kV converter station was less than 30 kV/m, the power frequency electric field was less than 4 kV/m, and the power frequency magnetic field strength wss less than 100 μT.Conclusion The electromagnetic environment level of ±800 kV converter station meets all standards.
作者 谢连科 臧玉魏 郭兆枫 马新刚 巩泉泉 尹建光 XIE Lianke;ZANG Yuwei;GUO Zhaofeng;MA Xingang;GONG Quanquan;YIN Jianguang(Electric Power Science Research Institute,Shandong Electric Power Company,Jinan 250002 China;Department of Environmental Science and Engineering,North China Electric Power University)
出处 《中国辐射卫生》 2019年第5期564-568,共5页 Chinese Journal of Radiological Health
关键词 特高压 换流站 电磁环境 Ultra-high Voltage Converter Station The Electromagnetic Environment
  • 相关文献

参考文献12

二级参考文献24

  • 1蔡俊超,金锡鹏.工频磁场与肿瘤[J].工业卫生与职业病,1995,21(4):251-252. 被引量:3
  • 2DL/T988-2005高压交流架空送电线路、变电站工频电场和磁场测量方法[S],2005. 被引量:18
  • 3粟福晰.高压输电的环境保护[M].北京:水利电力出版社,1989. 被引量:1
  • 4Wcrtheimer N .Eletrical Wiring Configurations and Childhood Cancer[J] .Epidermiology, 1979,109:273. 被引量:1
  • 5Fulton J.Electrical Wiring Configurations and Childhood Leukemia in Rhodeisland [J].Epiderrniology,1980,111 (3): 292. 被引量:1
  • 6Verkasalo P K .Risk of Cancer in Finnish Children Living Close to Power Lines [J].British Medical Journal,1993,307: 895. 被引量:1
  • 7Myers A .Childhood Cancer and Overhead Power Lines:a Case Control Study[J].British Cancer, 1990,62:1 008. 被引量:1
  • 8HJ/T24-1998,500kV超高压送变电工程电磁辐射环境评价技术规范[S]. 被引量:1
  • 9国家环保总局.HJ/T24-1998500kV超高压送变电工程电磁辐射环境影响评价技术规范[S].北京:中国环境科学出版社,1998. 被引量:3
  • 10HJ/T24-1998,500kV超高压送变电工程电磁辐射环境影响评价技术规范[S]. 被引量:54