关于UPS供电系统可靠度与可用性计算案例浅析 被引量:3

Brief Analysis on the Case of Reliability and Availability Calculation of UPS Power Supply System
下载PDF
导出
摘要 数据中心机房UPS供电系统可靠性要求越来越高,系统的可靠性和可用性一直是运维人员关注和重视的问题。本文从常见的二总线供电系统和三总线供电系统为例,进行了系统的可靠度与可用性对比分析和计算。再将降UPS容量的三总线供电系统进行了分析,其为典型的表决模型2/3(G)模型,降UPS容量的三总线供电系统的可靠度与可用性比二总线供电系统略高、又比三总线供电系统略低,正常工作时单台UPS负载率66.7%为最高,且投资成本适中,可以作为数据中心供电系统的首选。 The reliability requirement of UPS power supply system in data center is getting higher and higher.The reliability and availability of UPS power supply system have always been the focus of operation and maintenance personnel.In this paper,the reliability and availability of two-bus power supply system and three-bus power supply system are compared and analyzed.Then the three-bus power supply system with reduced UPS capacity is analyzed,which is a typical voting model 2/3(G)model.The reliability and availability of the three-bus power supply system with reduced UPS capacity are slightly higher than the two-bus power supply system and slightly lower than the three-bus power supply system.The load rate that is 66.7%of a single UPS is the highest in normal operation,and the investment cost is moderate,so it can be the first choice of power supply system in data center.
作者 余建宏 赵建平 YU Jian-hong;ZHAO Jian-ping(VertivTech(Xi’an)Co.,Ltd,Xi’an 710075;National Key Laboratory of Science and Technology on Blind Signal Processing,Chengdu 610041)
出处 《环境技术》 2019年第4期58-61,共4页 Environmental Technology
关键词 可靠度 可用性 MTBF 三总线供电系统 reliability availability MTBF three-bus power supply system
  • 相关文献

参考文献2

  • 1张广明,韩林编著..数据中心UPS供电系统的设计与应用[M].北京:人民邮电出版社,2008:276.
  • 2任立明主编..可靠性工程师必备知识手册[M].北京:中国标准出版社,2009:418.

引证文献3

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部