期刊文献+

某除湿车间空调系统改造分析

Analysis of Air Conditioning System Reform in a Dehumidification Workshop
下载PDF
导出
摘要 针对某除湿车间湿度无法达到设计值(≤70%)的情况,先对除湿系统室内、外设计参数进行探讨,阐述夏季空调室外设计参数不能作为除湿空调系统室外设计状态点。其次通过计算,表明维持室内的正压是保证室内相对湿度的关键因素,如果不维持正压,将带来大量的室外渗透湿负荷,给出维持室内正压所需最小新风量的计算。再次介绍除湿空调系统再热量的计算问题。 For a dehumidification workshop humidity cannot reach the design value (70%), firstly, the interior and exterior design parameters of dehumidification system are discussed. It come to the conclusion that the outdoor design parameters of air conditioning in summer cannot be used as the outdoor design status point of dehumidification air conditioning system. Secondly, the calculation shows that maintaining positive indoor pressure is the key factor to ensure indoor relative humidity, if the positive pressure is not maintained. It will bring a large amount of outdoor infiltration moisture load. The calculation of minimum fresh air volume required to maintain positive indoor pressure is given. Then the calculation problem of reheat in dehumidification air conditioning system is introduced.
作者 袁赟 YUAN Yun(Shanghai Investigation, Design & Research Institute Co., Ltd.)
出处 《建筑热能通风空调》 2019年第5期64-66,101,共4页 Building Energy & Environment
关键词 除湿车间 室内正压新风量 再热量 dehumidification workshop fresh air volume of indoor positive pressure reheating capacity.
  • 相关文献

参考文献2

二级参考文献19

  • 1余建华.关于回风再热技术的探讨[J].铁道工程学报,1996,13(1):133-136. 被引量:1
  • 2Khan A Y. Parametric analysis of heat and mass transfer performance of a packed type liquid desiccant absorber at part-load operating conditions [G] // ASHRAE Trans, 1996,102 : 349- 357. 被引量:1
  • 3Gandhidasan P. A simplified model for air dehumidification with liquid desiccant [ J ]. Solar Energy, 2004,76 : 409- 416. 被引量:1
  • 4Liu X H, Li Z, Jiang Y, et al. Annual performance of liquid desiccant based independent humidity control HVAC system[J]. Applied Thermal Engineering, 2006,26 : 1198-1207. 被引量:1
  • 5Liu X H, Jiang Y, Qu K Y. Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/ regenerator I- J 3. Energy Conversion . and Management, 2007,48 (2) : 546- 554. 被引量:1
  • 6Zhu Weifeng, Li Zhongjian, Liu Sheng, et al. In situ performance of independent humidity control air- conditioning system driven by heat pumps [-J]. Energy Buildings,2010,42(t0) : 1747-1752. 被引量:1
  • 7Pennington N A. Humidity changer for air conditioning.. US, 2700537[-P~. 1955. 被引量:1
  • 8Burns P R, Mitchell J W, Beckman W A. Hybrid desiccant cooling systems in super market applications[-G]///ASHRAE Trans, 1985, 91 (1B) : 457-468. 被引量:1
  • 9Sheridan J C, Mitchell J W. Hybrid solar desiccant cooling system[J-1. Solar Energy, 1985,34 (2) : 187 - 193. 被引量:1
  • 10Maclaine-cross I L. Proposal for a hybrid desiccant air-conditioning systemEG~//ASHRAE Trans, 1988, 94(2) : 1997- 2009. 被引量:1